Eaton CROUSE-HINDS Serie Nformación De Instalación Y Mantenimiento página 2

Ocultar thumbs Ver también para CROUSE-HINDS Serie:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Enclosure
Breaker / HMCP
size
options
Eaton EG
Eaton HMCPE
A
Eaton F-Frame
Eaton HMCP
Eaton EG
Eaton HMCPE
B
Eaton F-Frame
Eaton HMCP
Eaton JG
Eaton HMCPJ
C
Eaton F-Frame
Eaton HMCP
NOTE: AN19 NEMA size 4 with JG/HMCPJ breaker/HMCP only available from factory. AN19 NEMA 4 not available with F-Frame/HMCP .
NOTE: Starter overload is not preset and must be set at install.
CIRCUIT BREAKER/HMCP INSTALLATION
Consult instructions from circuit breaker/HMCP manufacturer before beginning installation.
The mounting plate and circuit breaker operator will accommodate breaker/HMCP
manufacturers and amperage ranges per Table 3. See Figure 2 for further assembly
details.
Circuit breaker /
Enclosure size
HMCP
Eaton EG
Eaton HMCPE
A
Eaton F-Frame
Eaton HMCP
Eaton EG
Eaton HMCPE
B
Eaton F-Frame
Eaton HMCP
Eaton JG
Eaton HMCPJ
C
Eaton F-Frame
Eaton HMCP
Table 3 – breaker manufacturers and amperages
HANDLE
(2) FORK PLATE SCREWS
(2) FORK PLATE LOCK WASHERS
FORK PLATE
1.
Install the circuit breaker/HMCP LINE side up. Using
the supplied mounting plate template sheet, identify
the circuit breaker/HMCP mounting holes in the
mounting plate. The mounting plate template is for
hole reference purposes only and should not be used
within the assembly. Use punched corner marks in
mounting plate (see Figure 3) to help locate circuit
breaker/HMCP . Figure 3 shows size A body. Similar
setup is used for sizes B and C.
2.
Secure the circuit breaker/HMCP to the mounting
plate with the screws provided from the circuit
breaker manufacturer (Eaton Series G circuit
breakers come with mounting hardware, Eaton Series C F-Frame circuit breakers do
not come with mounting hardware – use four (4) #8-32 x 1.50" long screws) (screws
not provided).
3.
After circuit breaker/HMCP
is installed, assemble the
appropriate fork plate to
the fork with supplied two
(2) 1/4-20 x 3/4" screws
and two (2) 1/4 split lock
washers as shown, and
1.50
38.1
torque screws to 30 in.-lb.
See Figure 4 and Table A4
for selecting the correct
fork plate for the assembly.
IF 1851 • 10/18
Starter options (see Note
below)
Eaton Freedom AN16 NEMA size 0-2
Eaton Freedom AN19 NEMA size 0-2
Eaton Space Savings AN13 NEMA size 0-2
Eaton Freedom AN16 NEMA size 3
Eaton Freedom AN19 NEMA size 3
Eaton Space Savings AN13 NEMA size 3
Eaton Freedom AN16 NEMA size 4
Eaton Freedom AN19 NEMA size 4
Eaton Space Savings AN13 NEMA size 4
Table 2 – empty enclosure sizes and associated manufacturers
Max. circuit
breaker / HMCP
Max. circuit
amperage
breaker / HMCP
recommended at
amperage frame
40°C
limit
70
125
50
100
70
225
50
150
125
125
100
100
125
225
100
150
200
250
150
250
200
225
150
150
(2) JAM NUTS
(2) END STOP SET SCREWS
LOCKOUT PLATE
BEARING
SHAFT
FORK SET SCREW
FORK
COVER NOT SHOWN
Figure 2
F-FRAME BREAKER
LOCATING CORNER
Figure 3
2.00
50.8
2.00
50.8
FORK PLATE
FORK PLATE
TYPE 1
TYPE 2
Figure 4
Copyright © 2018, Eaton's Crouse-Hinds Division
Transformer
External
options
ground lug
Eaton MTE
C0100E2A
Burndy KPA8C
C0100E4C
with Eaton PFK1 fuse kit
Eaton MTE
C0200E2A
C0200E4C
with Eaton PFK1 fuse kit
Burndy KPA25
Eaton MTE
C0300E2A
C0300E4C
with Eaton PFK1 fuse kit
4.
Attach the fork/fork plate assembly to circuit breaker/HMCP shaft as shown, and set
the height per reference Table A4 and Figure 5. Once the height is in place, torque
the set screw to 40 in.-lb. The fork plate should sit approximately 1/8"-3/16" above
the closest face of the circuit breaker.
5.
Visually inspect for proper alignment when closing cover to ensure the fork/fork plate
assembly properly engages the circuit breaker/HMCP toggle.
6.
Once the cover is closed, check the circuit breaker/HMCP operator, ensuring that the
operator properly functions by operating the circuit breaker/HMCP to the ON, OFF
and RESET positions.
7 .
Set up the handle stops in the lockout plate to allow proper travel and operation to
the circuit breaker/HMCP ON and RESET positions, but prevent over-travel. This
requires taking the handle to the circuit breaker/HMCP ON and RESET positions
and threading the set screws
to just contact the handle, then
tightening the jam nuts to lock
the set screws in place.
8.
Re-check the circuit breaker/
HMCP operator to ensure proper
operation of the circuit breaker/
HMCP to the ON/OFF/RESET
positions and no operator over-
travel.
9.
Finally, check the lockout to make sure that the circuit breaker/HMCP operator and
the circuit breaker/HMCP cannot be turned ON when locked out in the OFF position.
This should be checked at initial installation and whenever locking out the enclosure.
STARTER INSTALLATION
Consult instructions from starter manufacturer before beginning installation. The mounting
and reset operator will accommodate starter types and NEMA sizes per Table 4. See
Figure 6 for further reset assembly details.
1.
Install the starter LINE side up. Using the supplied mounting plate template sheet,
identify the starter mounting holes in the mounting plate. Mounting plate template
is for hole reference purposes only and should not be used within the assembly.
2.
Secure the starter to the mounting plate with the screws shown in reference Table
A3.
3.
After the starter is installed, assemble
the appropriate contact plate to the
EG BREAKER
reset operator adjustment shaft and set
LOCATING CORNER
the height per reference Table A5. The
contact plate should sit approximately
1/16"-1/8" above the reset button on
the starter. Once the height is in place,
torque the jam nut to 30 in.-lb.
4.
Once the cover is closed, check the reset
operator, ensuring that the operator
properly functions by resetting the starter.
Manually trip the starter and check that
the reset operator properly resets the
starter.
RESET PUSH BUTTON
RESET LEGEND PLATE
COVER NOT SHOWN
LOCK NUT
ADJUSTMENT SHAFT
2.00
50.8
CONTACT PLATE
JAM NUT
Terminal blocks
Heater options
Buchanan
terminal block
1546234-1
Ohmite 270 Series
2" heater with #9 brackets
Terminal block end
1546163-1
B
Figure 5
Encl.
size
Starter
Eaton Freedom AN16
A
Eaton Freedom AN19
Eaton Space Savings AN13
Eaton Freedom AN16
B
Eaton Freedom AN19
Eaton Space Savings AN13
Eaton Freedom AN16
C
Eaton Freedom AN19
Eaton Space Savings AN13
Table 4
RESET PUSH BUTTON
RESET LEGEND PLATE
COVER NOT SHOWN
LOCK NUT
CONTACT PLATE
ADJUSTMENT ADAPTER
JAM NUT
ADJUSTMENT SHAFT
AN19 NEMA SIZE 4 STARTER ONLY
R
NEMA
size
0-2
3
4
Figure 6
Page 2

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Crouse-hinds eic

Tabla de contenido