General Information; Clearances; Suspension; Gas Supply - HeatStar HSRR30SP(LP) Instrucciones De Operacion Y Manual Del Propietario

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

1. GENERAL INFORMATION

a.­Your­heater­comes­fully­assembled­and­is­tested­at­
the­factory­for­proper­gas­and­input­as­stated­on­
the­name­plate.
b.­ B efore­proceeding­with­the­installation,­be­sure­to­in-
spect­for­damages.­The­freight­company­that­delivered­
the­heater­must­be­notified­of­any­damages­prior­to­
installation.­HEATSTAR­will­send­replacement­parts­for­
damaged­parts­only­after­receiving­a­signed­inspection­
report­to­prove­the­liability­of­the­freight­company.
c.­Do­not­attempt­to­operate­heater­with­any­other­gas­
than­that­indicated­on­the­heater­name­plate.
d.­ I nstallation­of­the­heater­must­conform­with­local­
building­codes­or,­in­absence­of­local­codes,­with­
the­National­Fuel­Gas­Code,­ANSI­Z223.1/NFPA54.­In­
Canada,­refer­to­CAN­1-B146.1.
e.­Plugged­1/8"­N.P.T.­Test­Gage­Connection­is­located­on­
the­Gas­Valve­for­adjustment­purposes.­

2. CLEARANCES

Minimum clearances to combustibles. (Refer to Table 1)
Provide­adequate­clearance­to­combustibles,­Table­
1,­between­control­end­of­heater­for­servicing­
and­minimum­on­top­and­sides­for­ventilation­and­
combustion­air­supply.
A­minimum­clearance­of­8'­above­floor­for­public­
garages­in­accordance­with­ANSI/NFPA­No.­88­most­
recent­edition­or­Table­1;­whichever­is­larger.­In­Canada­
refer­to­CAN­1-B149.1­Installation­codes­for­Gas­
burning­appliances.
A­minimum­clearance­of­10'­from­the­bottom­of­
heater­to­top­of­wing,­or­engine­enclosure,­where­
aircraft­are­housed,­and­8'­above­floor­in­other­areas­
of­the­hanger­in­accordance­with­ANSI/NFPA­No.­409­
most­recent­edition,­or­Table­1;­the­larger­dimension­
of­ANSI/NFPA­No.­409­or­Figure­4­is­to­be­used.­In­
Canada­refer­to­CCA­B149-1-M91.
WARNING:
SHOWN­IN­TABLE­1­AND­FIGURE­4­OR­ON­HEATER­
NAMEPLATE,­IN­GARAGE­INSTALLATIONS­WHERE­
PARKED­VEHICLES­ARE­DIRECTLY­BELOW­THE­HEATER.

3. SUSPENSION

Heater­has­four­mounting­holes,­two­on­each­end,­for­
attaching­rod­or­supplied­brackets­and­shall­be­safely­
and­adequately­fixed­in­position­independent­of­gas­
and­electric­supply­lines.­Refer­to­Table­2­on­page­
4­and­Figures­4­and­5­on­page­5­for­recommended­
suspensions.

4. GAS SUPPLY

Provide­adequate­gas­supply­for­rated­input­of­each­
heater­using­American­Standard­Installation­of­gas­
piping­and­gas­appliances­in­building­ANSI/223.­1a/
392929_HSRR30-2017-WO-V9.indd 3
MAINTAIN­CLEARANCES­AS­
Enerco Group, Inc. | Gas-Fired Infra-Red Space Heaters
NFPA54­Pamphlet,­Table­C-3­shows­capacity­of­pipe­
of­different­diameters­and­lengths­in­cubic­feet­per­
hour­for­Natural­Gas­with­pressure­drop­of­0.3­inches­
specify­gravity­of­0.60.­For­liquefied­Petroleum­Gas­
(LP)­capacity­refer­to­Table­C-3­and­C-15­of­the­same­
pamphlet.­For­recommended­heater­gas­connection­
refer­to­Figure­No.­5,­Page­15.­In­Canada­refer­to­CAN­
1-B149.1,­and­CSA­B63.
If­gas­lines­are­to­be­pressure­tested­with­compressed­
air,­disconnect­each­heater­to­prevent­control­damage­
and­cap­outlets.­After­reconnecting­all­heaters,­purge­
gas­lines­of­air­and­check­all­connections­for­leaks­us-
ing­soap­solution.
WARNING:
DO­NOT­USE­MATCH­OR­OTHER­
FLAME­FOR­LEAK­TESTING.

5. PIPING REQUIREMENTS

All­piping­installed­must­comply­with­local­codes­and­ordinances­
or­with­the­National­Fuel­Gas­Code,­ANSI­Z223.1­(NFPA­54),­
whichever­takes­precedence.­When­installing­piping,­the­following­
requirements­must­be­taken­into­consideration:
•­ Use­new­properly­threaded­black­pipe­free­from­chips.
•­ Apply­a­pipe­compound­to­all­male­threads­prior­
to­assembly.­If­L.P.­gas­is­the­fuel,­ensure­that­pipe­
compound­is­resistant­to­L.P.­gas.­DO­NOT­USE­TEFLON­
™­tape.
•­ Prior­to­installation,­apply­pipe­compound­to­all­male­
threads­as­shown­in­Figure­1.
USE MODERATE AMOUNT OF PIPE DOPE
Figure 1. Pipe Compound Application
•­ Male­threads­on­pipe­to­be­installed­into­gas­valve­shall­
meet­the­requirements­of­Figure­2.­Threads­longer­than­
those­shown­in­the­figure­may­cause­gas­valve­distortion­
and­malfunction.
•­ A­sediment­trap­meeting­the­typical­requirements­of­
Figure­3­shall­be­installed­in­the­line­to­the­gas­valve.
•­ A­dedicated­shutoff­valve­for­the­heater­must­be­in-
stalled­in­the­gas­supply­line.
Figure 2. Gas valve connection requirements
E3
Operating Instructions and Owner's Manual
LEAVE­FIRST­2­THREADS­BARE
7/13/17 12:24 AM

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Hsrr30sp(ng)Hsrr30splp

Tabla de contenido