5.1

Warning and error messages during operation

The key indicated through Parameter
A0088 signals warnings A0008 + A0080, for example.
Key
A0000
No warning present.
A0001
Mains unit overloaded, warning key A0002 or A0004
A0002
Mains unit overload (60 s).
A0004
Short-term overload (1 s).
A0008
Max. heat sink temperature reached, check cooling system and fan.
A0010
Max. interior temperature reached, check cooling system and fan.
A0020
Output current, output current of mains unit is limited.
A0100
Mains phase failure, check mains fuses and supply cable.
A4000
DC link voltage has reached the type-specific minimum.
The error key saved after a fault in parameter
diagnosis easier.
The error message can be acknowledged via the control unit buttons and digital input S1IND.
Key
F00
00
No fault has occurred.
F01
02
Mains unit overloaded (60 s).
03
Short-term overload (1 s).
F02
00
Heat sink temperature too high, check cooling system and fan.
01
Temperature sensor defective or ambient temperature too low.
F03
00
Interior temperature too high, check cooling system and fan.
01
Interior temperature too low, check control cabinet heating.
F04
20
Mains frequency too high, mains frequency exceeds the limit set in parameter P1033
21
Mains frequency too low, mains frequency is below the limit set in parameter P1032
F05
00
Overcurrent; mains unit overloaded, check mains connection and filter.
05
Earth fault overcurrent, total of currents is not correct. Check cabling.
06
Overcurrent, quick triggering by hardware.
07
Overcurrent, slow triggering by software.
F07
00
DC link voltage too high, check deceleration ramps and connected brake resistor.
01
DC link voltage too low, check mains voltage.
02
Mains failure, check mains voltage and circuit.
03
Phase failure, check mains fuse and circuit.
04
Mains voltage UDC too high when turned on, check voltage.
05
Mains voltage BC too high when turned on, check voltage.
06
Mains voltage MC too high when turned on, check voltage.
06/13
Warnings
Warning messages
Error messages
Meaning
Overload
Heat sink
Interior
Frequency monitoring

Output current

DC link voltage
Quick Start Guide AEC
269 may be composed of several messages. Key
Meaning
310 makes troubleshooting and
Last error