Contact Closure Inputs; Contact Closure Wiring - Lutron Energi Savr Node Guia De Instalacion

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Energi Savr Node
Step 5: Contact Closure Inputs:
Emergency and CCI
WARNING! Danger of Shock. May result in serious injury
or death. DO NOT WIRE WHEN LIVE! Switch off power to all
power feeds via circuit breaker or isolator before wiring or
servicing the Energi Savr Node (ESN) with EcoSystem unit.
• Contact Closure (Emergency and CCI) wiring is IEC PELV / NECR
Class 2. Follow all applicable national and local codes for proper
circuit separation and protection.
• CCI input must be used with dry contact closure devices.
• Emergency input is normally closed (NC). The ESN with
EcoSystem unit is shipped with a jumper pre-installed.
• If the Emergency input is open, the ESN with EcoSystem unit will
enter Emergency Mode, which will force all ballasts and/or drivers
to their emergency level (100% by default) and disable control
from inputs and QS devices. When the closure is restored, ballasts
and/or drivers will return to their previous level.
Note: The ESN with EcoSystem unit will default to Emergency
Mode if the Emergency input is left open. If no Emergency
contact input is required, please leave the wire jumper in the
Emergency input terminals.
Lutron
6
|
®
with EcoSystem
TM
CCI – CONTACT CLOSURE INPUT
COM – COMMON
|
Installation Guide
®

Contact Closure Wiring

Contact Closure Wiring:
• 20 AWG to 12 AWG
(0.5 mm
to 4.0 mm
2
• Strip length: 1/4 in (6 mm)
• Torque: 5 in-lb (0.5 N
Energi Savr Node
with EcoSystem
TM
COM – COMMON
EMERG – EMERGENCY
)
2
m)
Installation Guide
®

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Qsn-1eco-sQsn-2eco-s

Tabla de contenido