Out Of Box Functionality - Lutron Energi Savr Node Guia De Instalacion

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Energi Savr Node
Simple application: Out of Box Functionality (requires no programming)
Zone 1
Occupancy
Sensor
Occupancy
Sensor
Perimeter
Interior

Out of Box Functionality

This section describes the default functionality that the unit will
present when first installed.
Inputs (Occupancy, Daylight, and IR):
Occupancy sensor/
IR Receiver
Connected to input
Controls link 1 only
group 1
Connected to input
Controls link 2 only
group 2
Connected to input
Controls both links
group 3
Connected to input
Controls both links
group 4
Connected to input
Controls link 1 only
groups 1, 3, or 4
(No out-of-box
functionality for Group 2)
Occupancy Sensors (Occ)
• Corresponding zones will turn on when the occupancy sensor is
in the occupied state (closed) and off when in the unoccupied
state (open).
Daylight Sensors (Daylight)
• Corresponding zone light levels will increase when light sensed
by daylight sensor decreases.
• Corresponding zone light levels will decrease when light sensed
by daylight sensor increases.
IR Receivers (IR)
• Corresponding zones respond to On, Off, Scene, Raise, and
Lower commands from compatible IR transmitters (see IR Re-
ceiver literature for compatible transmitters and EcoSystem
wallstations).
Energi Savr Node
with EcoSystem
TM
English
with EcoSystem
TM
Wired
Energi Savr
to input
Node with
group 1
EcoSystem
unit
Zone 2
Wired
to input
group 2
Daylight sensor
Controls link 1 only
Controls link 2 only
Controls both links
Controls both links
Controls link 1 only
Installation Guide
®
Español
Français
|
Installation Guide
®
Preconfigured mode (QSN-2ECO-S only)
Two zones with occupancy sensors
• Six fixtures shown on each link. However, up to 64 ballasts,
drivers, or EcoSystem devices can be connected per link.
• Each zone corresponds to one EcoSystem link.
Contact Closure Input (CCI)
• A ctivates a scene using a normally-open (NO) momentary clo-
sure from a dry contact closure device. Default scene sends all
fixtures to 100%.
Emergency Contact Closure Input (Emerg)
• Emergency contact closure input is normally closed (NC). The
Energi Savr Node (ESN) with EcoSystem unit is shipped with a
jumper pre-installed.
• If the Emergency input is open, the ESN with EcoSystem unit
will remain in Emergency Mode, which will force ballasts and
drivers to their emergency level (100% by default) and disable
control from inputs and QS devices.
• W hen the Emergency input is closed or jumpered, ESN with
EcoSystem unit ballasts and/or drivers will return to the settings
or levels they were at prior to entering Emergency Mode.
QS Wallstations
• All seeTouch
QS wallstations are Scene keypads by default.
®
• Scenes 1-16 will turn all the lights on to the preset levels shown
in the table below:
Scene #
Light Level: All Zones
1, 5-16
100%
2
75%
3
50%
4
25%
• Scene Off will turn all the lights Off.
Português
Lutron
9
|
®

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Qsn-1eco-sQsn-2eco-s

Tabla de contenido