Input Group Wiring - Lutron Energi Savr Node Guia De Instalacion

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Energi Savr Node
Step 4: Input group wiring
To connect a daylight sensor, occupant sensor, or infrared (IR) receiver, refer to the instruction sheets provided with the devices.
The diagram for the input terminals is shown below.
WARNING! Danger of Shock. May result in serious injury or death. DO NOT WIRE WHEN LIVE! Switch off power to all power
feeds via circuit breaker or isolator switch before wiring or servicing the Energi Savr Node with EcoSystem unit.
Buttons and LEDs in the unit are used for troubleshooting. If wiring is exposed when accessing buttons and LEDs, the unit
must be accessed by a certified electrician, following local codes.
Note: The ESN with EcoSystem unit accepts only one IR input (either daylight/IR sensor, IR receiver, or EcoSystem wallstation) per group.

Input Group Wiring

20 V: 20 V
Input Group Wiring:
• 22 AWG to 12 AWG
(0.5 mm
to 4.0 mm
)
2
2
• Strip length: 1/4 in (6 mm)
• Torque: 5 in-lb (0.5 N
m)
* Note: Only one IR device may be connected per input. If the IR signal from a
daylight sensor is connected, a wall control may not be connected to the same
input, and vice-versa.
** Connect the gray wire on -R model occupancy sensors.
Energi Savr Node
with EcoSystem
TM
English
with EcoSystem
TM
NOTE: There are four input groups. Each group has the
same inputs as shown in the diagram below.
Group 1 shown
Com: Common
IR: IR Receiver*
Daylight: Daylight Sensor
Occ: Occupancy Sensor
Note: Maximum wire run
length to each input not
to exceed 100 ft (30.4 m).
IR Transmitter
Installation Guide
®
Español
|
Installation Guide
®
Group 2 shown
Daylight/IR Sensor*
Occupancy Sensor
Français
Português
IR Transmitter
EcoSystem
Wallstation*
Lutron
5
|
®

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Qsn-1eco-sQsn-2eco-s

Tabla de contenido