Frequency Converter Operation - Wilo TOP-S Instrucciones De Instalación Y Funcionamiento

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Pump with terminal box type
OP-S
T
1
TOP-SD
(P
max ≤ 265 W)
1
TOP-RL
2
TOP-I
(P
max ≤ 265 W)
1
3
1~230 V
(320 W ≤ P
4
(320 W ≤ P
5
(650 W ≤ P
Pump with terminal box type
TOP-S
6
TOP-SD
(P
max ≤ 270 W)
1
TOP-I
7
3~400 V
(305 W ≤ P
• The setting of any thermal tripping that is fitted must correspond to the maxi-
mum current (see rating plate) of the speed stage at which the pump is being
operated.
Motor protection tripping devices
If Wilo tripping units SK 602 (N)/ SK 622 (N) are present in existing systems,
pumps with full motor protection (WSK) can be connected to them. Perform the
mains connection and also the tripping unit connection (refer to the rating plate
data) in accordance with the circuit diagram fig. 7a:
1~230 V: 320 W ≤ P

7.2.2 Frequency converter operation

Three-phase motors of the series TOP-S/-SD/-I can be connected to a fre-
quency converter. When operating with frequency converters, output filters
should be used to reduce noise and to avoid damage due to voltage spikes.
Installation and operating instructions Wilo-TOP-S/-SD/-RL/-I
Tripping
Internal switching off of
motor voltage
Internal switching off of
motor voltage
Thermal winding contact
and external tripping unit
max ≤ 400 W)
1
(SK602 (N)/ SK622 (N) or
other switch gear/control
device)
Thermal winding contact
and external tripping unit
max ≤ 400 W)
1
(SK602 (N)/ SK622 (N) or
other switchgear/control
device)
Thermal winding contact
and external tripping unit
max ≤ 960 W)
1
(SK602 (N)/ SK622 (N) or
other switchgear/control
device)
Tripping
Internal switching off of a
motor phase
Thermal winding contact
and external tripping unit
max ≤ 3125 W)
1
(SK602 (N)/ SK622 (N) or
other switchgear/control
device)
max ≤ 400 W, with thermal winding contact
1
Fault
acknowledgement
Automatically, after the
motor has cooled down
Automatically, after the
motor has cooled down
Manually at the tripping
unit, after the motor on the
SK602/SK622 has cooled
down on the SK602N/
SK622N: automatically
Manually at the tripping
unit, after the motor on the
SK602/SK622 has cooled
down on the SK602N/
SK622N: automatically
Manually at the tripping
unit, after the motor on the
SK602/SK622 has cooled
down on the SK602N/
SK622N: automatically
Fault
acknowledgement
• Switch off mains voltage
• Allow motor to cool down
• Switch on mains voltage
Manually at the tripping
unit, after the motor on the
SK602/SK622 has cooled
down on the SK602N/
SK622N: automatically
English
37

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Top-sdTop-rlTop-i

Tabla de contenido