Commands Table
Commands
Command Description
Read Temperature Internal
Read Temperature 2 External (optional)
Read Displayed Setpoint
Read Internal RTA1 – Internal RTA5
Read External RTA1 – External RTA5
Read Setpoint X (X = 1 to 5)
Read High Temperature Fault
Read High Temperature Warn
Read Low Temperature Fault
Read Low Temperature Warn
Read Proportional Heat Band Setting
Read Proportional Cool Band Setting
Read Integral Heat Band Setting
Read Integral Cool Band Setting
Read Derivative Heat Band Setting
Read Derivative Cool Band Setting
Read Temperature Precision
Read Temperature Units
Read Unit On
Read External Probe Enabled (optional)
Read Auto Restart Enabled
Read Energy Saving Mode
Read Time
Read Date
Read Date Format
Read Ramp Status (optional)
Read Firmware Version
Read Firmware Checksum
Read Unit Fault Status
Read Ramp Program (optional)
A-2
All messages from master and slave are terminated with a carriage return [CR]
Master
Sample Slave Response
Sends
(echo off)
RT
[V]C
RT2
[V]C
RS
[V]C
RIRTA1 – 5 [V]C
RERTA1 - 5 [V]C
RSX
[V]C
RHTF
[V]C
RHTW
[V]C
RLTF
[V]C
RLTW
[V]C
RPH
[V]%
RPC
[V]%
RIH
[V]Repeats per minute
RIC
[V]Repeats per minute
RDH
[V]Minutes
RDC
[V]Minutes
RTP
[V]
RTU
[V]
RO
[B]
RE
[B]
RAR
[B]
REN
[B]
RCK
hh:mm:ss
RDT
mm/dd/yyyy or
dd/mm/yyyy
RDF
mm/dd/yyyy or
dd/mm/yyyy
RRS
Stopped, Running,
Paused
RVER
[V]
RSUM
[V]
RUFS
[V1, V2 , V3, V4, V5]
See page A-5
RRP
[V1, V2 , V3, V4, V5]
See SRP on page A-4
Alternate units
F K
F K
F K
F K
F K
F K
F K
F K
F K
F K
C,F,K