Quick Installation

Plug the UPS into an outlet on a
1
dedicated circuit.*
NOTE! after you plug the UPS into a live AC outlet,
the UPS (in "Standby" mode) will automatically
charge its batteries,** but will not supply power to
its outlets until it is turned ON (see Step 3 below).
* Select models include an additional plug which can be switched by
a qualified electrician. ** The BATTERY CHARGE LED will be the
only LED illuminated.
Plug your equipment into the UPS.*
2
* Your UPS is designed to support only electronic equipment. You will
overload the UPS if the total VA ratings for all the equipment you con-
nect exceeds the UPS's Output Capacity. To find your equipment's VA
ratings, look on their nameplates. If the equipment is listed in amps,
multiply the number of amps by 120 to determine VA. (Example: 1 amp
× 120 = 120 VA). If you are unsure if you have overloaded the UPS's out-
lets, see "OUTPUT LOAD LEVEL" LED description.
Turn the UPS ON.
3
Press and hold the "ON/OFF/STANDBY" button for
one second. The alarm will beep once briefly after one
second has passed. Release the button.
1
2
3
4

Optional Installation

These connections are optional. Your UPS will function
properly without these connections. Note: Your unit may differ
slightly from these diagrams.
1
USB and RS-232 Serial
Communications
Use the included USB cable (see
1a
) and/or DB9 serial
cable (see
1b
) to connect the communication port on
your computer to the communication port of your
UPS. Install on your computer the Tripp Lite
PowerAlert Software appropriate to your computer's
operating system. Your UPS may feature additional
communications ports; these ports may also be connected
to additional computers which have PowerAlert
Software installed. Consult your PowerAlert manual
for more information.
Relay Contact-Closure Connection
2
Use the included DB9 cable (see
2a
cialized electronic equipment to the relay contact-closure
port on your UPS System.See diagram (
below to determine signals carried by this port.
Relay Contact Closure Chart
Line Fail
Mid Battery
Indication
Indication
UPS Operating
Pins 1
Pins 2
Pins 7
Pins 8
Conditions
& 6
& 6
& 3
& 3
AC Input Voltage OK
CLOSED
OPEN
AC Input Out of Range
OPEN
CLOSED
Battery More than 3 Min.
OPEN
CLOSED
Remaining Charge*
Battery Less than 3 Min.
CLOSED
OPEN
Remaining Charge*
Battery More than 2 Min.
Remaining Charge*
Battery Less than 2 Min.
Remaining Charge*
Open on
Close on
Close
Open
Line
Line
Below
Below
Contact Action
Failure
Failure
Mid
Mid
Battery
Battery
Battery
* Times are approximate, at full load.
EPO Port Connection
3
(Select Models Only)
This optional feature is only for those applications
which require connection to a facility's Emergency
Power Off (EPO) circuit. When the UPS is connected to
this circuit, it enables emergency shutdown of the
UPS's inverter.
Using the cable provided, connect the EPO port of your
UPS (see
3a
) to a user-supplied normally closed or nor-
mally open switch according to the circuit diagram (see
3b
). The EPO port is not a phone line surge suppressor;
do not connect a phone line to this port.
1a
1b
) to connect spe-
2b
) and chart
2a
Low Battery
Relay Contact Closure Interface Diagram
Indication
NO TE :
Pins 4
Pins 5
TOP OF DUAL
DB9 (J5/J34)
J5
& 9
& 9
REMOTE CONTACTS
1
K1 A
6
LINE FAIL
2
7
K4 A
3
MID BAT
8
4
OPEN
CLOSED
K1 0A
9
LO BATT
CLOSED
OPEN
5
2b
Close
Open
Below
Below
Low
Mid
Battery
Battery
3a
3b
5
OPENS ON LINE FA IL
COM
CLOSE S ON LINE FAIL
CLOSES BELOW MID BAT TERY
COM
OPENS BELOW MID BATTERY
CLOSES BELOW LOW BATTER Y
COM
OPENS BELOW LOW BATTERY
4-5