Tripp-Lite PDU3EVN3L2130 El Manual Del Propietario página 14

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Features
C13
LED Configuration
Standard
1
Red Flashing
Red Flashing
Alternate
Green Flashing
1 This is the default configuration.
Push-to-Reset Guard
21-03-434-93349E.indb 14
21-03-434-93349E.indb 14
C19
Outlet Status LED: Once the unit is powered on, each outlet individually
ramps up and each Outlet Status LED will illuminate when the associated
outlet is ready to distribute live AC power.
LED Color
Outlet Status
Off
Off
Green
On
Yellow
On
Red
Off
Off
Off
Off
Red
On
On
Green
Off
Off
Circuit Breaker (Select Models): There are 3 Load Banks, each
protected by a circuit breaker. If the connected equipment load exceeds
the Maximum Load Rating for those banks of the PDU, the circuit breaker
will trip. Disconnect excess load and reset the breaker.
Note: Each breaker comes equipped with a push-to-reset guard to prevent
accidental breaker tripping. To turn off the breaker, insert a flathead screwdriver into
the reset slot.
Mounting Brackets: Use these brackets as an alternate PDU mounting
method.
Mounting Buttons: Located on the back side of the PDU, the pre-
installed buttons are used for toolless mounting.
Note: Four additional mounting buttons are included for alternate rack styles.
PDUMVROTATEBRKT Mounting Accessory: Use these L-shaped
brackets to mount the PDU with its outlets facing the rear of the rack.
Outlets: During normal operation, the outlets
distribute AC power to connected equipment.
Description
Outlet power is absent
Circuit breaker is on – Outlet power is present
Outlet's current has exceeded 80% of the outlet current
rating – Outlet power is present
Outlet's voltage is below the Low Voltage threshold – Outlet
power is absent
Circuit breaker has tripped – Outlet power is absent
Outlet power is absent
Circuit breaker is on – Outlet power is present
Outlet's current has exceeded 80% of the outlet current
rating – Outlet power is present
Outlet is disabled – Outlet power is absent
Circuit breaker has tripped – Outlet power is absent