Installation
2-2A
Corded Models - Connect the input
plug to your facility's compatible AC
power source and input connection.
2-2B
Hardwire Models (PDU3XEVSRHWA and PDU3XEVSRHWB only)
WARNING
Only qualified personnel should perform hardwire installations. Wire codes and
requirements differ from area to area. Be sure to conform to local electrical
requirements. Use of copper wiring with ferrules is recommended for AC input
terminal connections. Each input terminal connection should be torqued to the
listed specification. Improperly sized wiring, inadequate torque, or use of non-
copper wiring can result in overheating of input terminal connections.
These models do not come equipped with an input cable. Conduit and adapters are
installed to the endplate
terminal block, located behind the access plate
Model
PDU3XEVSRHWA
PDU3XEVSRHWB
To access the terminal block to make input wire connections, remove the access plate
located on the rear side of the PDU
conduit and torque wire connections to listed torque specifications.
A
Remove Access Plate Screws
C
21-03-434-93349E.indb 8
21-03-434-93349E.indb 8
, wires are channeled through the conduit and adapters to the
A
Recommended Wire Gauge / Type
#6 AWG Copper Wire (13.3 mm
. Ferruled wire ends are recommended. Secure
C
B
8
2-2A
.
B

Torque Specifications

)
12.2 in•lbf (1.38 N•m)
2
Ground Terminal
2-2B
Plug type may
vary by model.
X
Y
Z
N
4/5/2021 4:11:48 PM
4/5/2021 4:11:48 PM