4. Operation
Max charge current: The Max charge current is set and defaulted at the factory for UPS models with internal batteries
when operating without an external battery cabinet (S3M10K1B, S3M10K2B, S3M10K3B, S3M15K2B, S3M15K3B,
S3M20K3B). However, to connect an external battery cabinet, consult the battery cabinet manual for the specific UPS
configuration required based on the specific battery cabinet model.
Cell float voltage (V/Cell): The float voltage value can be 2.23 to 2.30 V/cell, and is 2.27 V/cell by default.
Cell boost voltage (V/Cell): The battery equalized voltage value can be 2.30 to 2.40 V/cell, and is 2.35 V/cell by default.
Aver charging Duration (min): Boost charge time limit. The value can be 1 to 999 minutes, and is 240 by default.
Note: Average Charging Duration (min) is set and defaulted to 240 min. (4 hours) at the factory for UPS models with internal batteries
when operating without an external battery cabinet (models S3M10K1B, S3M10K2B, S3M10K3B, S3M15K2B, S3M15K3B,
S3M20K3B). However, to connect an external battery cabinet, consult the specific battery cabinet manual for the detailed UPS
configuration required for the specific battery cabinet model.
EOD Battery Volt (0.01V/Cell): End of discharge voltage. The value can be 1.60 to 1.90. The default is 1.67
Float Temp Compen Coeff: Modify the voltage of compensation after enabling the switch. The value can be 0.001V/cell
to 0.007V/cell. The default is 0.003V/cell.
Boost Charge Setting: Boost charge disable or enable setting. The default is enable.
No Battery Warning: When set to Disable, the buzzer will not sound. Set to Enable for audible battery warnings. The
default is Enable.
Figure 4-28B: Battery Setup