Single Input Power Cable Connection - Tripp-Lite SmartOnline S3M10K1B Manual Del Propietário

Sistemas ups trifásicos
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

3. Installation and Wiring
Table 3.5: Battery Cabinet Batteries and Breakers. All battery cabinets are ISTA-3B tested.
Battery Cabinet Model
BP240V09 / 09K
BP240V09-NIB
BP240V40
BP240V40L
BP240V40-NIB
BP240V40L-NIB

3.12 Single Input Power Cable Connection

Once the equipment has been positioned and secured, connect the power cables as described in the procedure below.
Verify the UPS is totally isolated from its external power source and that all power isolators of the UPS are open. Ensure they
are electrically isolated, and post any necessary warning signs to prevent their independent operation.
Remove the terminal block cover to access the UPS system's input, output and grounding connection terminals. Then connect
the wires according to the terminal block diagram shown below. Connect the grounding/earthing wires first when making other
wire connections.
Notes:
• Ensure the wires are connected tightly and securely to the terminals.
• Install the output breaker between the output terminal and the load. The breaker should be qualified with leakage current protective
function.
• Cabling should be protected by flexible conduit and routed through the appropriate knockouts in the terminal block cover.
• Be sure to also add an equipotential bonding wire between the UPS and the external battery cabinets.
Batteries Included
Battery Quantity and Ah Capacity
Yes
No
Yes
Yes
No
No
80 x 9Ah
Designed for 80 x 9Ah
20 x 40Ah
40 x 40Ah
Designed for 20
(CSB GP12400i) x 40AH
Designed for 40
(CSB GP12400i) x 40Ah
28
Breakers
1 x 125A, 3 Pole
2 x 160A
1 x 125A, 3 Pole
2 x 160A
1 x 250A, 3 Pole
4 x 250A
1 x 250A, 3 Pole
4 x 250A
1 x 250A, 3 Pole
4 x 250A
1 x 250A, 3 Pole
4 x 250A
Fuses

Publicidad

Tabla de contenido

Solución de problemas

loading

Tabla de contenido