Magnetostrictive Linear Position Sensor – Rod Style
Shielding and cable routing
Defined ground!
The BTL and the control cabinet must be at the
same ground potential.
Shielding
To ensure electromagnetic compatibility (EMC), observe
the following:
Connect BTL and controller using a shielded cable.
Shielding: Braided copper shield with minimum 85%
coverage.
Cable version: On the BTL side, the cable shielding is
connected to the housing. Ground the cable shielding
on the controller side (connect with the protective earth
conductor).
Strand version: Observe note on shielding.
Magnetic fields
The position measuring system is a magnetostrictive
system. Ensure that there is sufficient distance between
the BTL, holding cylinder and strong, external magnetic
fields.
Cable routing
Do not route the cable between the BTL, controller, and
power supply near high voltage cables (inductive stray
noise is possible). The cable must be routed tension-free.
Min. bending radius (BTL6-...-KA_ _)
Fixed routing
Cable length
The maximum cable length is 2 m
5) Prerequisite: Construction, shielding and routing preclude the effect of
any external noise fields.
Accessories
PUR cable, 4-wire, shielded, molded
Straight
BCC M415-0000-1A-014-PS0434-...
Example with 5 m:
BCC M415-0000-1A-014-PS0434-050
Angled
BCC M425-0000-1A-014-PS0434-...
Pin
Color
1
BN Brown
2
WH White
3
BU Blue
4
BK Black
www.balluff.com
3 x cable Ø
5)
.
Startup
DANGER
Uncontrolled system movement
When starting up, if the position measuring system is
part of a closed loop system whose parameters have not
yet been set, the system may perform uncontrolled
movements. This could result in personal injury and
equipment damage.
► Persons must keep away from the system's
hazardous zones.
► Startup must be performed only by trained technical
personnel.
► Observe the safety instructions of the equipment or
system manufacturer.
1. Check connections for tightness and correct polarity.
Replace damaged connections.
2. Turn on the system.
3. Check measured values and adjustable parameters
(especially after replacing the BTL or after repair by the
manufacturer). Recalibrate the BTL, if necessary.
Operating notes
Regularly check function of the BTL and all associated
components.
Take the BTL out of operation whenever there is a
malfunction.
Secure the system against unauthorized use.
Note on EMC characteristics
EMC characteristics can only be ensured if the
BTL is completely installed in a grounded metal
housing.
Type code
BTL6-...-ZA0R, BTL6-...-ZA0N:
Modular flange connector, M12, 4-pin
Material: brass, nickel-plated
BTL6-...-ZA16, BTL6-...-ZA17:
Modular flange connector, M12, 4-pin
Material: stainless steel l
english