Installing temperature sensors
Heating applications
Pipe bend
Applications and flowmeter installation place
The flowmeter must be mounted in accordance with the instructions given in the relevant flowmeter operating instructions.
Installation place of the flowmeter must be as stated on the energy calculator nameplate, i.e. in the cold pipe (low
temperature) or the hot pipe (high temperature), see menu loop 3.
Pulse input setting
The calculator pulse input (IN0) setting must fit the flowmeter pulse output. Check both nameplates for the settings, see also
menu loop 3 for the FUE950 settings.
Flowrate
The maximum flowrate for the energy calculator must not be exceeded (see nameplate).
Electrical connection
1. Remove top of device and prepare cable entries.
FUE950 Energy calculator
A5E03652942-002, 04/2014
Cooling applications
Straight pipe
①
Pipe wall
②
Insulation
③
Welded sleeve (prepared by installer)
④
Sensor pocket
⑤
Insulation seal for sensor
⑥
Pt500 (4-wire) temperature sensor
3