4.6 Installation of condense pipes
As for the cold condensate pipe of central air conditioning indoor unit, the following factors were considered
major:
(1) Displacement of large condensate
(2) Incidental loss of cooling capacity
(3) Maintenance is inconvenient during installation, wind cross can occur from this location.
1. The material of condensate pipe can be chosen among U-PVC pipe or galvanization pipes. Health,
rust and other issues should be considered, U-PVC pipe is recommended to be adopted.
2. The installation requirements:
1) Water seal must be installed at the outdoor drain and be fixed.
2) The slope of drain pipe should be ≥1%.
3) Indoor section of the condensate pipe should put on a pipe insulation or be wrapped with cotton
insulation.
4) After condensate pipe installation, irrigation leak test must be performed. Confirm no water leakage
in various joints and smooth drainage. The installation can be performed with reference to figure 18:
4.Installation guide
Thermal insulation
Indoor unit
Condensate pipe
Slope> 1%
Water seal
h:1cm/100Pa
Ground
Figure 18