Install The Drainpipe - Infiniton CCFL-4530 Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Model
Liquid pipe Gas pipe
18K
Φ6.35
24
36K
Φ9.52
/
48
55K
Φ9.52
/
Piping and banding
Piping and banding
①Band the power cables, the signal wires and the connecting pipe.
② Adjust the positions for in-piping and out-piping according
to the wall-hole position. Determine the pipe outing style.
③ The banded pipe should insert from the outdoor side through
the wall-hole to the indoor side. It is must be carefully to do the
piping, without damaging the pipe and the thermal insulation layer.
During the banding, do not pull the snake-shape pipe too hard.
During the pipe bending, cut off the needed irregularity on
the heat insulation sleeve in the bend point, and then show
up the pipe (band it with the bandage after bending). The
radius of the bend should be as big as possible, to avoid
reshaped or pressed bad.
Stretching the pipe, use the vinyl tape to fix 5 to 6 positions.
Under the occasion of laterally extract the pipe, it should
cover the heat insulation material.
It should avoid banding the joints of connecting pipe, just for the
leakage check.
Connecting pipe
Tear out 10cm-15cm of the thermal insulation sleeve in out-pipe and in-pipe of indoor
unit, make it convenient for pipe connecting. Firstly, connect the low-pressure pipe, and then the high-pressure
pipe. Press the tapered surface of the pipe to the connector vertically, twist the connectors to the bottom of the
bolt, and then fix it tight with a torque wrench.

◆Install the drainpipe

When delivery, the outfall is PVC pipe, when connecting, please
use the subsidiary of sealing materials and sleeve.
Be sure to take the heat insulation of drainpipe of the indoor
unit, if no heat insulation, it will have the condensate. The
connecting part of indoor unit also needs heat insulation.
Connecting the drainpipe, it should use the rigid PVC
adhesive, and make sure there is no water leakage
phenomenon.
4.Installation guide
A
B
Φ12.7
1245
680
Φ15.88
1245
680
Φ15.88
1670
680
Outside diameter of
the copper pipe (mm)
Φ9.52 or Φ9
Φ12.7 or Φ12
14
C
D
E
244
760
450
244
760
450
244
760
450
Connecting cable
Bent the pipe with the
thumb
The minimum radius 100 mm
Tightening
torque ( N·cm)
Φ6.3 or Φ6
1570 (160kgf·cm )
2940 (300kgf·cm )
4900 (500kgf·cm )
Φ16
7360 (750kgf·cm )
Φ19
9720 (900kgf·cm )
Heat insulated
material
Unit: mm
F
G
H
1119
200
240
1119
200
240
1542
200
240
Connecting piping
Bandage tape
Reinforce tightening
torque ( N·cm)
1960 (200kgf·cm )
3430 (350kgf·cm )
5390 (550kgf·cm )
7850 (800kgf·cm )
11860 (1210kgf·cm )
Tilt down for
above 1/100

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Ccfl-6321

Tabla de contenido