Surge Protective Device (SPD)
Module for DeviceNet
Cat. No. 3863-DEV
INSTALLATION INSTRUCTIONS
DI-003-03863-20A
Module limiteur de surtensions transitoires
(LST) pour systèmes DeviceNet
N° de cat. 3863-DEV
DIRECTIVES
Protector de Sobretensión (PST
Para Sistemas DeviceNet
No. De Cat. 3863-DEV
INSTRUCCIONES DE
INSTALACION
LIMITED 10 YEAR WARRANTY AND EXCLUSIONS
Leviton warrants to the original consumer purchaser and not for
the benefit of anyone else that this product at the time of its sale
by Leviton is free of defects in materials and workmanship under
normal and proper use for ten years from the purchase date.
Leviton's only obligation is to correct such defects by repair or
replacement, at its option, if within such ten year period the product
is returned prepaid, with proof of purchase date, and a description
of the problem to Leviton Manufacturing Co., Inc., Att: Quality
Assurance Department, 59-25 Little Neck Parkway, Little Neck,
New York 11362-2591. This warranty excludes and there is
disclaimed liability for labor for removal of this product or
reinstallation. This warranty is void if this product is installed
improperly or in an improper environment, overloaded, misused,
opened, abused, or altered in any manner, or is not used under
normal operating conditions or not in accordance with any labels
or instructions. There are no other or implied warranties of any
kind, including merchantability and fitness for a particular purpose,
but if any implied warranty is required by the applicable jurisdiction,
the duration of any such implied warranty, including merchantability
and fitness for a particular purpose, is limited to ten years. Leviton
is not liable for incidental, indirect, special, or consequential
damages, including without limitation, damage to, or loss of use
of, any equipment, lost sales or profits or delay or failure to perform
this warranty obligation. The remedies provided herein are the
exclusive remedies under this warranty, whether based on
contract, tort or otherwise.
For Technical Assistance Call:
1-800-824-3005
www.leviton.com
DI-003-03863-20A
ENGLISH
DESCRIPTION
The Leviton Surge Protective Device Module (SPD) for DeviceNet, Cat. No. 3863-DEV, is designed as the primary line of protection from DeviceNet
line impulses and transients.
The SPD is to be connected as a series unit in the DeviceNet DC voltage and data line. Use two plug-in, 5-pin screw terminal connectors
(provided) for Input and Output connection of Cat. No. 3863-DEV.
SPECIFICATIONS
Maximum DC Operating Voltage: 19.8V DC
Clamping Voltage:
L-G: 22Vpk
L-L: 7Vpk
Maximum Surge Current: 1kA
Strike Breakdown Voltage:
100 V/Micro Sec
100 V/Sec
L-G:
17.0 - 29.9 V
12.8 - 19.2 V
L-L:
7.18 - 8.92 V
2.62 - 3.36 V
Maximum Capacitance A-B Lines:
L-L: 20 pF
Operating Temperature Range:
-10°C to 85°C
Storage Temperature Range:
-20°C to 85°C
Relative Humidity:
0 to 95% non-condensing
Altitude: -1000 ft. to 15000 ft.
Tested to UL 497B
• Solid state semi-conductor SPD circuitry for: 3863-DEV (Line H and L protection and DC Voltage) to Ground.
• SPDs are enclosed in a non-conductive ABS case. ABS is a flame retardant thermoplastic, compliant with UL 746C polymeric material test requirements.
TO INSTALL
WARNING:
TO BE INSTALLED, ASSEMBLED AND/OR USED IN ACCORDANCE WITH APPLICABLE ELECTRICAL CODES AND REGULATIONS.
WARNING:
IF YOU ARE NOT SURE ABOUT ANY PART OF THESE INSTRUCTIONS, CONSULT A QUALIFIED ELECTRICIAN.
WARNING:
TO AVOID FIRE, SHOCK, OR DEATH; TURN OFF POWER AT CIRCUIT BREAKER OR FUSE AND TEST THAT THE POWER
IS OFF BEFORE WIRING.
WARNING:
INCORRECT ASSEMBLY OR INSTALLATION MAY RESULT IN FIRE, ELECTRICAL PROPERTY DAMAGE, SHOCK,
PERSONAL INJURY, OR DEATH.
SYSTEM VOLTAGE REQUIREMENTS
SPDs are intended for use in DeviceNet applications and allow approximately a 15 VDC potential difference. Maximum continuous operating
voltage is 19.8 VDC.
LOCATION AND MOUNTING
1. TURN OFF POWER at the installation location by turning the subject device power OFF and unplugging the DeviceNet (DEV) equipment cabling.
2. Locate the DEV SPD so that the connectors can be easily inserted into the SPD without excessive tension on the wiring connections (Figure 3).
Use the two slotted "feet" to mount housing.
NOTE: For optimum performance, locate the DeviceNet SPD close to the equipment to be protected.
3. Connect the DEV SPD to chassis ground using the metallic base plate and/or the attached braided cable. DO NOT ADD ANY EXTENSION
TO THE "BRAIDED CABLE TO GROUND" PATH.
WIRING PROCEDURES
CAUTION:
TURN OFF EQUIPMENT POWER AND DISCONNECT THE DATA CABLE WHERE SPD PROTECTION IS REQUIRED.
NOTE: Drop lines are used to connect devices in a DeviceNet Cable System. These instructions are intended for Drop lines using DeviceNet
"Thin Cable", although, "Thick Cable" may also be used. If another type of cabling is used, wire colors may be different. Care must be taken to
ensure the correct electrical function is connected to the DEV SPD Input and Output terminals (Figure 2).
Cut the cable, as shown in Figure 4, and connect each end to the DEV SPD Input and Output connectors as follows (Figures 1- 2):
1. Slip a large diameter piece of shrink tubing jacket over the cut ends of the data cable.
NOTE: DO NOT cut the drain wire shorter than the other wires, it is used for connection to the "SHLD" (Shield) terminal.
2. Remove 1" (2.54 cm) of the braided shield under the PVC jacket and cut back any insulation strands.
3. Separate the wires and remove 0.32" (.81 cm) of insulation off the end of the Red-Black pair.
4. Separate the wires and remove 0.32" (.81 cm) of insulation off the end of the Blue-White pair.
NOTE: Unless otherwise directed by existing wiring system requirements perform steps 5 to 9 as shown in Figure 2. Be sure to tighten
retaining screws for each wire.
5. Tin the strands and insert the Red wire into terminal V+.
6. Tin the strands and insert the White wire into terminal CAN+.
7. Tin the strands and insert the Blue wire into the terminal CAN- location.
8. Tin the strands and insert the Black wire into the terminal V- location.
9. Insert the shield/drain wire (non-jacketed) into terminal SHLD.
10. Position the shrink tubing to prevent the end of shield from fraying and apply the necessary heat to shrink it tight.
11. Plug the connectors into the appropriate "Input" and "Output" locations on the DEV SPD module, as shown in Figures 2 and 3.
NOTE: Although Input and Output connectors are wired identically, they plug-in to the SPD facing opposite directions. Verify proper wiring
after attaching connectors per Figures 2 and 3.
12. Reconnect the modified equipment cable as shown in Figure 4.
POWER ON: Following data cable reconnection to the equipment, restore power to the installation circuit by turning the power ON. INSTALLATION
IS COMPLETE.
FRANÇAIS
DESCRIPTION
Ce module LST est conçu pour assurer la protection des lignes DeviceNet des effets dévastateurs des surtensions transitoires et des impulsions électriques.
Sur ces lignes de transmission de données à courant continu, ses entrées et sorties doivent être raccordées en série au moyen des connecteurs à
cinq broches fournis.
FICHE TECHNIQUE
Tension maximale de fonctionnement en courant continu : 19,8 V c.c.
Tension de blocage :
L-T : 22 V (crête)
L-L : 7 V (crête)
Courant transitoire maximal : 1 kA
Surtension d'amorçage :
100 V/ µs
100 V/ s
L-T :
17,0 à 29,9 V
12,8 à 19,2 V
L-L :
7,18 à 8,92 V
2,62 à 3,36 V
Capacité maximale (lignes A-B) :
L-L : 20 pF
Températures de fonctionnement :
de -10 à 85° C
Températures de rangement :
de -20 à 85° C
Humidité relative :
de 0 à 95 % (sans condensation)
Altitude : de -300 à 4 500 m
Conformité éprouvée à la norme UL497B
• Circuits de limitation transistorisés à semi-conducteurs pour les lignes (L) H, L et c.c. à la terre (T).
• Logement non conducteur en thermoplastique ABS ignifuge, conforme aux exigences de la norme UL746C en matière de matériaux polymérisés.
INSTALLATION
AVERTISSEMENT :
INSTALLER, ASSEMBLER OU UTILISER CONFORMÉMENT AUX CODES DE L'ÉLECTRICITÉ APPLICABLES.
AVERTISSEMENT :
À DÉFAUT DE BIEN COMPRENDRE LES PRÉSENTES DIRECTIVES, EN TOUT OU EN PARTIE, ON DOIT FAIRE
APPEL À UN ÉLECTRICIEN QUALIFIÉ.
AVERTISSEMENT :
POUR ÉVITER LES RISQUES D'INCENDIE, DE CHOC ÉLECTRIQUE OU D'ÉLECTROCUTION, COUPER LE COURANT
AU FUSIBLE OU AU DISJONCTEUR ET S'ASSURER QUE LE CIRCUIT SOIT BIEN COUPÉ AVANT DE PROCÉDER À L'INSTALLATION.
AVERTISSEMENT :
LES ERREURS D'ASSEMBLAGE OU D'INSTALLATION PEUVENT ENTRAÎNER DES DOMMAGES MATÉRIELS,
DES CHOCS ÉLECTRIQUES, DES BLESSURES CORPORELLES OU UNE ÉLECTROCUTION.
TENSIONS NOMINALES
Convenance aux applications DeviceNet où la différence de potentiel est d'environ 15 V c.c. au plus. Tension maximale de fonctionnement
continu de 19,8 V c.c.
CHOIX DE L'EMPLACEMENT ET INSTALLATION :
1. COUPER LE COURANT au lieu d'installation en mettant le dispositif visé hors tension et en débranchant le câblage DeviceNet (DEV) de
l'équipement.
2. Installer le module LST de manière à ce que les connecteurs puissent y être aisément insérés sans créer trop de tension sur les raccords
(figure 3). Se servir des deux supports à fente pour installer le logement.
REMARQUE : pour un rendement optimal, il faut placer le module LST le plus près possible de l'équipement à protéger.
3. Raccorder le module à la masse au moyen de la plaque métallique ou du câble tressé. NE PAS TENTER DE RALLONGER LE
PARCOURS À LA MASSE DE CE CÂBLE.
CÂBLAGE
MISE EN GARDE :
METTRE L'ÉQUIPEMENT HORS TENSION ET DÉCONNECTER LE CÂBLE DE TRANSMISSION DE DONNÉES LÀ
OÙ LA PROTECTION DU MODULE EST REQUISE.
REMARQUE : On se sert de fils d'embranchement pour raccorder les divers dispositifs qui forment les systèmes DeviceNet. Les directives
suivantes s'appliquent aux installations où ces fils d'embranchement sont des câbles « minces », mais on peut aussi avoir recours à des câbles
plus « épais ». Cependant, si on utilise une autre sorte de câble, les couleurs données pourraient ne pas correspondre. Quoiqu'il en soit, il
importe surtout de s'assurer que les bonnes fonctions électriques soient raccordées aux bornes d'entrée et de sortie du module LST (figure 2).
Couper le câble de la manière illustrée à la figure 4 et connecter chaque extrémité aux connecteurs du module, comme suit (figures 1 et 2).
1. Glisser un morceau de gaine thermorétrécissable de diamètre élevé sur les extrémités coupées du câble de transmission de données.
REMARQUE : NE PAS couper le fil de masse plus court que les autres (il doit être connecté à la borne SHLD).
2. Retirer près de 2,54 cm (1,0 po) du blindage tressé sous la gaine en PVC, et couper les brins d'isolant restants.
3. Séparer les fils et dénuder sur 0,81 cm (0,32 po) l'extrémité des fils de la paire rouge/noir.
4. Séparer les fils et dénuder sur 0,81 cm (0,32 po) l'extrémité des fils de la paire bleu/blanc.
REMARQUE : à moins que le système en présence ne l'exige autrement, on doit réaliser les étapes 5 à 9 de la manière illustrée à la figure 2.
Il faut en outre s'assurer de bien serrer les vis de retenue pour chaque fil.
5. Étamer les brins et insérer le fil rouge dans la borne « V+ ».
6. Étamer les brins et insérer le fil blanc dans la borne « CAN+ ».
7. Étamer les brins et insérer le fil bleu dans la borne « CAN- ».
8. Étamer les brins et insérer le fil noir dans la borne « V- ».
9. Insérer le fil de masse/blindage (sans gaine) dans la borne « SHLD ».

Publicidad

loading

Resumen de contenidos para Leviton 3863-DEV

  • Página 1 DESCRIPTION The Leviton Surge Protective Device Module (SPD) for DeviceNet, Cat. No. 3863-DEV, is designed as the primary line of protection from DeviceNet Ce module LST est conçu pour assurer la protection des lignes DeviceNet des effets dévastateurs des surtensions transitoires et des impulsions électriques.
  • Página 2 1-800-648-3332 (Sólo en E.U.A.) NOTE: DeviceNet Thick Cable may be substituted colors are identical • Circuito la línea de semi-conductor de estado sólido para: 3863-DEV a tierra (protección de Línea Fase y Línea y Voltaje de CD). Brass Terminal Plate Connected to Ground www.leviton.com...
  • Página 3 FOLD SCHEME 17.0¨ LEVI LEVITON INSTRUCTION SHEET/MANUA ON INSTRUCTION SHEET/MANUAL SPECIFIC SPECIFICATION TIONS DI-003-03863-20A Black Front Panel Cat. No. Helvetica 11.0¨ 50 Lb. offset Paper size: Paper size: 11" X 17 " Overall size: Overall size: 3.6" X 3.4" Final fold size:...