420010239602 Multicalor 45 ÷ 140 PR/PR
EN
Red blink code of
signal lamp (LED))
2 blinks
3 blinks
4 blinks
5 blinks
6 blinks
7 blinks
8 blinks
9 blinks
10 blinks
14 blinks
To calculate the burner's working output, in kW, proceed as follows:
- Check at the meter the quantity of supplied litres and the duration,
in seconds, of the reading, then calculate the burner's output through
the following formula:
1 - PUMP
2 - SAFETY OIL VALVE
3 - OIL VALVE
4 - RETURN OIL VALVE
5 - NOZZLE
6 - GAS PRESSURE SWITCH
7 - SAFETY GAS VALVE
8 - GAS VALVE
Min gas pressure switch
The gas pressure switch has the function to check that the gas pressure before the gas
valve does have the minimum pressure to make the burner running correctly.
Unscrew off and remove cover M.
- Set knob N to a value equal to 60% of gas nominal feed pressure (i.e. for natural gas
nom. pressure = 20 mbar, set knob to a value of 12 mbar; for LPG nom. pressure of
G30/G31- 30/37 mbar, set knob to a value of 18 mbar). Screw up cover M.
Air pressure switch calibration
The air pressure switch is provided for monitoring the pressure of the
combustion air fan. Unscrew screws A and B and remove cover C.
• Adjust the combustion with air pressure switch (APS) set at minimum.
• Start to obstruct the air inlet with a paper paying attention to O2 and CO values red
on the analyzer.
• Progressively increase air inlet obstruction till the CO valve is slightly more than 1000
ppm. Stop obstruction in this position.
• Increase APS setting up to burner lock out.
• Now the APS is set to avoid CO production during the combustion.
• Remove air obstruction and fit again APS cover C.
Error code table
«AL» at
Possible cause
term. 10
on
No establishment of flame at the end of «TSA»
- Faulty or soiled fuel valves - Faulty or soiled flame detector
- Poor adjustment of burner, no fuel - Faulty ignition equipment
on
«LP» faulty
- Loss of air pressure signal after «t10», - «LP» welded in normal position
on
Extraneous light when burner is started up
on
Time out «LP»
- «LP» welded in working position
on
Free
on
Too many losses of flame during operation
(limitation of the number of repetitions)- Faulty or soiled fuel valves.
- Faulty or soiled flame detector - Poor adjustment of burner.
on
Free
on
Free
off
Wiring error or internal error, output contacts, other faults.
on
CPI contact not closed
CALCULATION OF WORKING OUTPUT OF THE BURNER

GAS CIRCUIT

e x f = kW
s
VGS
6
7
VgS
1
2
Suction
A
Return
R
VgR
4
16
e =
Litres of gas
s =
Time in seconds
G20 = 34,02
G25 = 29,25
f
G30 = 116
G31 = 88
VG
8
Vg
3
5
N
M
I
L
D
C
A
H
G
B
F
E