Use only the suitable box wrench provided for this operation to remove the nozzle, taking care to not damage the elec-
trodes. Fit the new nozzle with the same care. Note: Always check the position of electrodes after having replaced the
nozzle (see illustration). A wrong position could cause ignition troubles.
The control of the detector current shall be carried out by plugging a microampe-
rometer with full scale at 1000 µA (D.C.) in series with the UV-cell. If the detec-
tor current is too low verify the connection between phase and neutral of the bur-
ner and the grounding of the burner itself. Minimum required detector current is
200 µA.
F
SAL
HLBT
0
1
R
HLoil
SAMA
V
B
HLgas
SAgG
R
SA s.r
NOZZLE CLEANING AND REPLACEMENT
FLAME DETECTOR SYSTEM CHECK
REMOVING THE BLAST TUBE
DESCRIPTION OF CONTROL PANEL
D
RWF 50
0: OFF
1: ON
G
C
0=STOP
1=UP
2=LOW
3=AUTO
E
0=STOP
1=OIL
2=GAS
3=AUTO
A
420010239602 Multicalor 45 ÷ 140 PR/PR
6 mm
SW = BLACK
BL = BLU
A - reset key
B - operating lamps (orange=light-oil; green= gas)
C - selector:
OUT = loking of devoices for operating at intermediate outputs
UP
= operation at max. output
LOW = operation at min. output
= automatic operation
AUTO
D - ON/OFF switch
E - selector:
0 = STOP
1 = light-oil operation
2 = gas operation
3 = automatic operation
F - termal lock-out lamp