2.2 Other Default Settings
Setting
Default Value
IP Address
Obtain via DHCP
User Name and Password User Name: admin Password: admin (For Version 12.04.0030 and Above)
User Name: guest Password: guest
User Name: admin Password: [blank] (For Versions 12.03.0024 and 12.04.0019)
Telnet Access
Enabled (SSH Access: Enabled)
Web Access
Enabled (SSL Access: Disabled)
SNMP Access
Enabled for Version 12.04.0040 and above
Disabled for Previous Versions
Default SNMP Access for 12.04.0040 and above
Community
tripplite
public
Temperature High &
Shut Down UPS System 2 Minutes After Event
Battery Low Event
E-mail Notification
Not Configured
SNMP Traps
Not Configured
Time
Use Onboard Clock (Set Manually)
Event Logging
Enabled
Data Logging
Disabled
Ramp/Shed
Remain off / Remain on (not configured)
SYSLOG
Disabled
2.3 SNMP Configuration
SNMPWEBCARD allows a compatible UPS system or PDU to function as an SNMP-managed device on your network, using the SNMP agent and
Management Information Base (MIB). The SNMP agent resides in the SNMPWEBCARD firmware and responds to standard SNMP commands
(Get, Get Next and Set). It can also generate SNMP traps (messages). The MIB determines which parameters can be monitored and controlled. Two
MIB files—Tripplite.mib and RFC1628.mib—must be loaded on each Network Management Station that will monitor the managed device. (The files
are provided on the CD-ROM included with the SNMPWEBCARD or network-enabled PDU. Consult your Network Management Station software
documentation for instructions on how to import MIB files.)
3. Web Console
The Web console is the primary graphical user interface for the SNMPWEBCARD.
3.1 Opening the Web Console
1.
Open a Web browser that supports frames, forms and Java.
2.
Type the IP address assigned to the SNMPWEBCARD or PDU into
the address field and press the enter key. (Refer to the printed manual
for IP address assignment instructions.)
3.
You should be prompted for a user name and password (Figure
3-1). The default administrator user name is admin and the default
password is admin.
4.
After you enter the user name and password, the status page (Figure
3-3) will appear in the browser window.
Note: Pages update automatically every 30 seconds. Reload/refresh
a page manually to update sooner.
Access Type
Network Access SNMP Version
read/write all
v2c
read only all
v1
Figure 2-2: Default SNMPWEBCARD Settings
3
Additional Information
3.9 Settings > Network
3.10 Settings > System
3.9 Settings > Network
3.9 Settings > Network
3.9 Settings > Network
3.7 Settings > Events
3.7 Settings > Events
3.9 Settings > Network
3.10 Settings > System
3.11 Logs > Events
3.12 Logs > Data
5.0 Load Ramping and Shedding
3.9 Settings > Network
Figure 3-1: Web Console Login