3.4 Actions > Control
Click the "Actions" menu button and the "Control" submenu button to
display the Actions > Control page. Click the "Controls" tab (Figure
3-7) to see commands that you can execute immediately or schedule for
automatic execution. To execute a command immediately, select it from the
drop-down menu and click the "Execute" button. To schedule a command,
select it from the drop-down menu, set the desired time and frequency
parameters and click the "Schedule" button.
If the command you select from the drop-down menu has operational
parameters that you can modify, they will be shown in the "Parameters"
area. You can click the editable variables and type new values to change
the settings for the command. If you plan to change the command
parameters, you should change them before you execute the command or
add it to the command schedule.
Available commands include "Reboot UPS," "Initiate Self-Test," "Cycle
All Loads," "Cycle Load," "Turn Load Off," "Turn Load On," "Turn All
Figure 3-7: Actions > Control > "Controls" Tab
Loads Off," and "Turn All Loads On". For a complete list of commands
available for your device, refer to the drop-down menu.
Click the "Schedules" tab (Figure 3-8) to see a list of scheduled commands.
To remove a scheduled command, check the box next to the command and
click the "Delete Selections" button.
Figure 3-8: Actions > Control > "Schedules" Tab
3.4.1 Actions > Control > Economy Mode
Economy Mode
When a SmartOnline UPS System operates in on-line mode, it continuously
converts AC input power to DC (battery) power and converts DC power to
regulated AC output power. Continuous double conversion produces ideal
output, but does not provide maximum efficiency.
In Economy Mode (available on select models), the UPS system increases
efficiency by implementing dynamic double conversion, which means it
suspends or resumes double conversion automatically as the quality of input
power changes. As long as input power quality is satisfactory, the UPS system
suspends double conversion and operates with maximum efficiency. If input
power quality deviates from the designated safe operating range, the UPS
system resumes double conversion until input power quality improves.
You can turn Economy Mode on or off at any time, from any location. You can
also schedule Economy Mode, allowing the UPS system to provide maximum
protection during peak hours and maximum efficiency during off-peak hours.
Figure 3-9: Actions > Control > "Controls" Tab > Set Economy Mode
Enabling Economy Mode:
To put a Tripp Lite SmartOnline UPS System into Economy Mode, go to the
"Actions" menu button and the "Control" submenu button. Select either "Enable
Economy Mode" or "Set Economy Mode", depending on the UPS. If the UPS
has "Set Economy Mode", enter a "1" in the "Parameters-Value" field and then
click the "Execute Command" button. On the front panel of the UPS system, the
"LINE" and "LOAD" LEDs will illuminate green and the "BYPASS" LED will
illuminate a solid yellow when the UPS system is in Economy Mode. Models
with LCD display will indicate Economy Mode status in the LCD screen.