Features
Transformer
A
Transformer Rear Panel
A
AC Output Terminal Block: Use these terminals to connect
the transformer to the circuit that supplies your equipment with
AC power. Remove the terminal block cover for access.
B
AC Input Terminal Block: Use these terminals to connect the
transformer to the utility AC power source. Remove the
terminal block cover for access.
C
"FROM UPS" Terminal Block: Use these terminals to
connect the transformer to the preinstalled wiring harness
connected to the detachable PDU. Remove the terminal block
cover for access. Refer to the wire and terminal labeling to
identify corresponding wires and terminals.
D
"TO UPS" Terminal Block: Use these terminals to connect
the transformer to the preinstalled wiring harness connected to
the detachable PDU. Remove the terminal block cover for
access. Refer to the wire and terminal labeling to identify
corresponding wires and terminals.
E
Thermal Breaker: This breaker trips if the transformer's
temperature is too high. Allow it to cool before resetting.
External Battery Pack
External Battery Pack Rear Panel
201102089 93-2982.indb 7
continued
B
A
B
C
D
F
AC to UPS Breaker: This double-pole circuit breaker controls
the transformer's AC output to the power module.
G
Output Breaker: This triple-pole circuit breaker controls the
transformer's AC output to the circuit that supplies your
equipment with AC power.
H
Manual Bypass Switch: This switch is used to bypass the
power module, allowing you to repair or replace the power
module without powering down connected equipment. When
the switch is set to "BYPASS" the transformer's AC input is
connected to the AC output. Connected equipment will continue
to receive AC power through the transformer, but will not
receive battery backup in the event of an outage.
I
Input Voltage Select Switch: Use this switch to set the
transformer's input voltage. Remove the cover for access.
A
Battery Pack to UPS Connector: Insert the male battery
connector at the end of the battery pack cable into the power
module's female battery connector.
B
Additional Battery Pack Connector: Insert the male battery
connector from an additional battery pack into this female
battery connector to provide extended runtime. Remove the
cover for access. Multiple battery packs (BP240V10RT3U) can
be daisy-chained to provide as much runtime as required.
7
G
E
H
F
I