Tripp-Lite SmartOnline SU10KRT3U El Manual Del Propietario página 9

Ocultar thumbs Ver también para SmartOnline SU10KRT3U:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Connection
Connect Transformer to AC Output Circuit
1
Pass user-supplied cabling through the junction box's left
knockout (1.25" diam.) and connect it to the transformer's AC
A
output terminals
.
2
Refer to the AC output voltage labeling above the transformer's
A
AC output terminals
will provide voltage appropriate for your equipment. Connect the
other end of the cable to the output circuit that will supply your
equipment with AC power.
Connect Transformer to AC Power Source
High Voltage Warnings
Warning: Make sure the breaker for the UPS system's AC power
source is turned off before proceeding. Failure to de-energize the input
circuit will result in the continued risk of injury or death from contact
with high voltage.
1
Pass user-supplied cabling through the junction box's middle
knockout (1.25" diam.) and connect it to the transformer's AC
A
input terminals
. Connect the other end of the cabling to the
AC power source.
2
Reattach the transformer's junction box
3
Confirm the transformer's input voltage setting by removing the
C
switch cover
above the input voltage selection switch. Set the
switch to 208V if necessary, then reattach the switch cover.
Facility Input
Transformer Input Voltage Setting
Voltage
(Rear Panel Switch)
240V AC
240V AC
208V AC (Default)
208V AC (Default)
200V AC
240V AC
201102089 93-2982.indb 9
continued
to determine which terminal connections
B
.
Power Module Input Voltage Setting
(Control Panel LCD)
240V AC
208V AC (Default)
200V AC
A
1
B
1-3
9
A
2
C
A
A
Transformer Detail