SMA Sunny Tripower 15000TL Instrucciones Para La Sustitución página 27

Ocultar thumbs Ver también para Sunny Tripower 15000TL:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 114
SMA Solar Technology AG
3. If the DC protective cover has not been attached
yet, reattach it. Tighten all 4 screws with an Allen
key in the order 1 to 4 (AF 3, torque:3.5 Nm).
4. Connect the communication assembly with the
inverter. To do so, plug the ribbon cable to the
communication assembly and lock it.
5. Connect the DC connectors to the inverter. Observe the recorded position of the DC
connectors.
☑ The DC connectors snap into place.
6. Seal all unused DC inputs using the DC connectors with sealing plugs.
7. Insert the lower enclosure lid from above and flip it
down. The screws must protrude from the lower
enclosure lid.
8. Tighten all 6 screws with an Allen key in the order 1
to 6 (AF 3, torque: 2.0 Nm ± 0.3 Nm). By
tightening the screws in the prescribed order, you
avoid warping the enclosure lid, which would keep
it from sealing correctly. Tip: If the screws fall out of
the lower enclosure lid, insert the long screw into the
hole at position 6, and the 5 short screws into the
other holes.
Replacement Manual
8 Recommissioning the Inverter
STPTLEE-STPTL-10-BPDCLS-RM-xx-10
27