SC-JBS-S-A
Splice Connection with Junction Box Installation Instructions
APPROVALS
Hazardous Locations
Class I, Div. 2, Groups A, B, C, D
Class II, Div. 2, Groups F, G
Class III
– WS
09-IEx-0008X
Ex e IIC T* Gb
(2)
Ex e II T* (see schedule)
IECEx
Ex tD A21 IP66
IECEx BAS 06.0049X
KIT CONTENTS
Item Qty
Description
A
1
Stand assembly
B
1
Cable lubricant
C
12
Tape strips
D
2
Green/yellow tubes
E
4
Coils Kester
48 core LF solder for nickel
®
F
12
Thomas & Betts splices, spares included
G
1
Junction box
H
1
Lid
I
1
Spanner
J
1
Strain relief
WARNING:
This component is an electrical device that must be installed
correctly to ensure proper operation and to prevent shock or
fire. Read these important warnings and carefully follow all of
the installation instructions.
• To minimize the danger of fire from sustained electrical
arcing if the heating cable is damaged or improperly
installed, and to comply with the requirements of nVent,
agency certifications, and national electrical codes,
ground-fault equipment protection must be used. Arcing
may not be stopped by conventional circuit breakers.
• Be sure all power sources are de-energized before
opening box.
• Keep components and heating cable ends dry before and
during installation.
(1)
Ex e II T
– WS
(1)
for T-Rating, see design
documentation
• Component approvals and performance are based on the
use of nVent-specified parts only. Do not use substitute
parts or vinyl electrical tape.
• Soldering tools or torches can cause fire or explosion
in hazardous areas. Be sure there are no flammable
materials or vapors in the area before using these tools.
• Damaged conductors can overheat or short. Do not
break conductor wire strands when scoring the jacket or
removing insulation.
• Use only fire-resistant insulation materials, such as
fiberglass wrap or flame-retardant foam.
• Wrap exposed conductors with supplied tape strips to
prevent shorts.
DESCRIPTION
The nVent RAYCHEM SC-JBS-S-A is a NEMA 4X-rated splice
connection kit designed for use with nVent RAYCHEM 2 and 3SC30,
40, 50 (-CT), 2 and 3SC/H30, 40, 50 (-CT) and 2 and 3SC/F30, 40, 50
(-CR) series heating cables in hazardous locations.
This kit may be installed at temperatures as low as –40°F (–40°C).
For easier installation, store above freezing until just before installation.
For technical support, call nVent at (800) 545-6258.
TOOLS REQUIRED
• Diagonal cutters
• Wire strippers
• Solder tool or torch (with small tip)
• Thomas & Betts TBM5S crimp tool (P/N P000000585) or
WT2000 crimp tool (P/N 273435-000) tool or equivalent.
Crimp tools can be ordered from nVent.
ADDITIONAL MATERIALS REQUIRED
• Pipe straps (2)
• Glass cloth tape:
– GT-66 for installation temperature above 40°F (4°C)
– GS-54 for installation temperature above –40°F (–40°C)
OPTIONAL MATERIALS
• Recommended conduit drain:
JB-DRAIN-PLUG-3/4IN   (P/N 278621-000)
• Pipe adapter to increase stand height:
SC-JB-PIPE-ADAPTER   (P/N P000000648)
A
B
C
D
E
F
HEALTH HAZARD: Hot solder can burn eyes and skin.
Fumes during soldering are irritating to eyes and may cause
headache and respiratory system irritation or damage.
Prolonged or repeated exposure to rosin flux fumes during
soldering may result in allergic reaction in a sensitive person,
resulting in asthma symptoms. Consult MSDS VEN 0043 for
further information.
CHEMTREC 24-hour emergency telephone: (800) 424-9300
Non-emergency health and safety information:
(800) 545-6258
• Slotted screwdriver
• Utility knife
J
I
H
G
CAUTION:

Publicidad

loading

Resumen de contenidos para nVent RAYCHEM SC-JBS-S-A

  • Página 1 DESCRIPTION The nVent RAYCHEM SC-JBS-S-A is a NEMA 4X-rated splice connection kit designed for use with nVent RAYCHEM 2 and 3SC30, 40, 50 (-CT), 2 and 3SC/H30, 40, 50 (-CT) and 2 and 3SC/F30, 40, 50 (-CR) series heating cables in hazardous locations.
  • Página 2 NVENT RAYCHEM HEATING CABLE TYPES Heating Cable Construction 2 and 3SC30, 40 and 50 (-CT) 2 and 3SC/H30, 40 and 50 (-CT) 2 and 3SC/F30, 40 and 50 (-CR) Outer jacket Outer jacket Tinned-copper braid Tinned-copper braid Inner jacket Inner jacket...
  • Página 3 • Remove 3/4-inch (20 mm) insulation and fiberglass • Push braid forward. Use a braid from end of each conductor. screwdriver to open braid. 3SC heating cable shown. 3/4 in. • Bend heating cable and work it (20 mm) through opening in braid. Fiberglass 3SC heating cable shown.
  • Página 4 • Place junction box onto • Remove box nut. stand. Align key-ways in box hole with alignment feature on stand. • Put box nut back onto stand. • Tighten box nut with spanner. O-ring • Slide strain relief over heating cable, down onto box nut.
  • Página 5 • Crimp heating cable conductors together and use only the specified crimp tool, die and splices to ensure a proper electrical connection (see table). Improperly crimped connection can result in overheating. • Smooth down any sharp wires after crimping to prevent wires from poking through tape strips in Step 17. Thomas &...
  • Página 6 IMPORTANT: To ensure proper electrical insulation, use the specified high temperature Teflon tape provided with the kit. Do not use common vinyl tape which does not have adequate temperature rating. 3rd & 4th tape strips 2nd tape strip 1st tape strip Remove and discard release liners while...
  • Página 7: Ferramentas Necessárias

    Conexão De Ligação Com Caixa De Ligação Instruções De Instalação DESCRIÇÃO O nVent RAYCHEM SC-JBS-S-A é um kit de conexão de ligação com classificação NEMA 4X destinado às séries de unidades de elementos aquecedores nVent RAYCHEM 2 e 3SC30, 40, 50 (-CT), 2 e 3SC/H30, 40, 50 (-CT) e 2 e 3SC/F30, 40, 50 (-CR) em...
  • Página 8 NVENT RAYCHEM TIPOS DE UNIDADE DE ELEMENTO AQUECEDOR Estrutura da unidade de elemento aquecedor 2 e 3SC30, 40 e 50 (-CT) 2 e 3SC/H30, 40 e 50 (-CT) 2 e 3SC/F30, 40 e 50 (-CR) Capa externa Capa externa Blindagem de cobre estanhado Blindagem de cobre estanhado...
  • Página 9 • • Empurre a blindagem para a frente. Remova 20 mm (3/4 pol.) do isolamento e da Use uma chave de fenda para abrir a blindagem de fibra de vidro na ponta de cada condutor. blindagem. Unidade de elemento aquecedor 3SC mostrada na figura.
  • Página 10 • Coloque a caixa de • Remova a ligação no suporte. Alinhe porca da caixa. as chavetas no furo da caixa ao dispositivo de alinhamento no suporte. • Coloque a porca da caixa novamente no suporte. • Aperte a porca da caixa com uma chave de porca.
  • Página 11 • Crimpe os condutores da unidade de elemento aquecedor e use apenas a ferramenta de crimpagem, a matriz e as ligações especificadas para garantir uma conexão elétrica adequada (consulte a tabela). A crimpagem incorreta da conexão pode resultar em superaquecimento. •...
  • Página 12 IMPORTANTE: Use a fita Teflon especificada para altas temperaturas fornecida no kit para garantir o isolamento elétrico apropriado. Não use fitas comuns de vinil que não apresentam a especificação de temperatura adequada. Remova e descarte o papel 1ª tira de fita 2ª...
  • Página 13: Aprobaciones

    El nVent RAYCHEM SC-JBS-S-A es un kit de conexión de empalmes con calificación NEMA 4X diseñado para su uso con cables calefactores nVent RAYCHEM serie 2 y 3SC30, 40, 50 (-CT), 2 y 3SC/ H30, 40, 50 (-CT) y 2 y 3SC/F30, 40, 50 (-CR) en lugares peligrosos.
  • Página 14 NVENT RAYCHEM TIPOS DE CABLES CALEFACTORES Construcción del cable calefactor 2 y 3SC30, 40 y 50 (-CT) 2 y 3SC/H30, 40 y 50 (-CT) 2 y 3SC/F30, 40 y 50 (-CR) Chaqueta exterior Chaqueta exterior Malla de cobre estañado Malla de cobre estañado...
  • Página 15 • Empuje la malla hacia delante. Utilice • Retire 20 mm (3/4 pulgadas) de aislamiento y de malla de un destornillador para abrir la malla. fibra de vidrio del extremo de cada conductor. Se muestra el cable calefactor 3SC. • Doble el cable calefactor y páselo por 20 mm la abertura de la malla.
  • Página 16 • Coloque la caja de • Retire la tuerca conexiones eléctricas de caja. sobre el soporte. Alinee las ranuras del orificio de la caja con la indicación de alineación del soporte. • Vuelva a colocar la tuerca de caja en el soporte. •...
  • Página 17 • Crimpe los conductores de cable calefactor y utilice sólo la herramienta crimpadora, el troquel y los empalmes especificados para garantizar una conexión eléctrica adecuada (consulte la tabla). Una conexión crimpada de manera incorrecta puede sufrir sobrecalentamiento. • Después de crimpar un cable suavice los hilos afilados para que no perforen las tiras de cinta en el Paso 17. Empalme Thomas &...
  • Página 18 IMPORTANTE: Para asegurar un aislamiento eléctrico adecuado, utilice la cinta de Teflon especificada para alta temperatura que se suministra en el kit. No utilice cinta de vinilo común que carezca de una capacidad nominal de temperatura adecuada. 1era tira de Retire y deseche el protector de las tiras 2nda tira 3era y 4ta tiras...