(2) Units "ft" and "oz"
<Formula>
•
When the piping length from the outdoor unit to the farthest HBC controller is
10 m (32 ft) or shorter
Amount of
High-pressure pipe
additional
ø7/8 total length
=
charge (oz)
× 2.48 (oz/ft)
Outdoor unit model
(E)M200
(E)M250
(E)M300
+
(E)M350
(E)M400
(E)M450
(E)M500
* Amount of refrigerant to be charged for
single-module units
•
When the piping length from the outdoor unit to the farthest HBC controller is
longer than 10 m (32 ft)
Amount of
High-pressure pipe
additional
ø7/8 total length
=
charge (oz)
× 2.05 (oz/ft)
Outdoor unit model
(E)M200
(E)M250
(E)M300
+
(E)M350
(E)M400
(E)M450
(E)M500
* Amount of refrigerant to be charged for
single-module units
<Example>
Outdoor unit model: PURY-EM300YNW-A1
Main HBC controller 1 model: CMB-WM108V-AA
Main HBC controller 2 model: CMB-WM108V-AA
Sub HBC controller model: CMB-WM108V-AB
* Refer to the pipe connection examples in Fig.2.4.2 (P.2).
A
: ø5/8; 59 ft
1
A
: ø5/8; 16 ft
2
A
: ø5/8; 32 ft
3
B: ø5/8; 26 ft
The total length of the high-pressure piping and liquid piping in each case is as fol-
lows:
ø5/8 total length: 59 (A
)
1
ø5/8 total length: 16 (A
) + 32 (A
) + 26 (B) = 74
2
3
Therefore, when the piping length from the outdoor unit to the farthest HBC con-
troller is longer than 10 m (32 ft),
Amount of additional charge = (133 × 0.57) + 99 × 2
= 327.1 oz (Fractions are rounded up.)
12
High-pressure pipe
High-pressure pipe
ø3/4 total length
ø5/8 total length
+
+
× 1.73 (oz/ft)
× 1.19 (oz/ft)
Amount
Amount (oz)
(oz/HBC controller)
+
36
99
36
0
0
0
0
0
High-pressure pipe
High-pressure pipe
ø3/4 total length
ø5/8 total length
+
+
× 1.36 (oz/ft)
× 0.97 (oz/ft)
Amount
Amount (oz)
(oz/HBC controller)
+
36
99
36
0
0
0
0
0
■ (E)P200 to 500YNW (R410A refrigerant)
(1) Units "m" and "kg"
<Formula>
•
When the piping length from the outdoor unit to the farthest HBC controller is
30.5 m (100 ft) or shorter
Amount of
High-pressure pipe
additional
=
ø22.2 total length
charge (kg)
× 0.23 (kg/m)
Outdoor unit model
(E)P200
(E)P250
(E)P300
+
(E)P350
(E)P400
(E)P450
(E)P500
* Amount of refrigerant to be charged for
single-module units
•
When the piping length from the outdoor unit to the farthest HBC controller is
longer than 30.5 m (100 ft)
Amount of
High-pressure pipe
additional
=
ø22.2 total length
charge (kg)
× 0.21 (kg/m)
Outdoor unit model
(E)P200
(E)P250
(E)P300
+
(E)P350
(E)P400
(E)P450
(E)P500
* Amount of refrigerant to be charged for
single-module units
(2) Units "ft" and "oz"
<Formula>
•
When the piping length from the outdoor unit to the farthest HBC controller is
30.5 m (100 ft) or shorter
Amount of
High-pressure pipe
additional
=
ø7/8 total length
charge (oz)
× 2.48 (oz/ft)
Outdoor unit model
(E)P200
(E)P250
(E)P300
+
(E)P350
(E)P400
(E)P450
(E)P500
* Amount of refrigerant to be charged for
single-module units
•
When the piping length from the outdoor unit to the farthest HBC controller is
longer than 30.5 m (100 ft)
Amount of
High-pressure pipe
additional
ø7/8 total length
=
charge (oz)
× 2.27 (oz/ft)
Outdoor unit model
(E)P200
(E)P250
(E)P300
+
(E)P350
(E)P400
(E)P450
(E)P500
* Amount of refrigerant to be charged for
single-module units
High-pressure pipe
High-pressure pipe
+
ø19.05 total length
+
ø15.88 total length
× 0.16 (kg/m)
× 0.11 (kg/m)
Amount
Amount (kg)
(kg/HBC controller)
+
0
3.0
0
0
0
0
0
0
High-pressure pipe
High-pressure pipe
+
ø19.05 total length
+
ø15.88 total length
× 0.14 (kg/m)
× 0.10 (kg/m)
Amount
Amount (kg)
(kg/HBC controller)
+
0
3.0
0
0
0
0
0
0
High-pressure pipe
High-pressure pipe
+
ø3/4 total length
+
ø5/8 total length
× 1.73 (oz/ft)
× 1.19 (oz/ft)
Amount
Amount (oz)
(oz/HBC controller)
+
0
99
0
0
0
0
0
0
High-pressure pipe
High-pressure pipe
ø3/4 total length
ø5/8 total length
+
+
× 1.52 (oz/ft)
× 1.09 (oz/ft)
Amount
Amount (oz)
(oz/HBC controller)
+
0
99
0
0
0
0
0
0