11. Insert the lower enclosure lid from above and flip it
down. The screws must protrude from the lower
enclosure lid.
12. Tighten all 6 screws in the order 1 to 6 (hex socket,
AF3, torque: 2.0 Nm) By tightening the screws in
the prescribed order, you avoid warping the
enclosure lid, which would keep it from sealing
correctly. Tip: If the screws fall out of the lower
enclosure lid, insert the long screw into the lower
middle hole and the 5 short screws into the other
holes.
13. Set the DC load-break switch to position O so that
both mounting screws are visible.
14. Insert the DC load-break switch firmly into the intended opening on the inverter. During this
process, the DC load-break switch must still be in position O and aligned so that the screws
are positioned over the threads.
15. Tighten the 2 screws (torque: hex socket, AF3,
torque2.0 Nm).
Replacement Manual
8 Recommissioning the Inverter
STPTL-30-H-AC-CON-RM-xx-10