1: Connect data bus
The maximum cable length permitted for the data bus is 100ft/30m.
Connect the RX+ terminal on the TL8803GI to the TX+ terminal on the PCL-422
l
Connect the RX- terminal on the TL8803GI to the TX- terminal on the PCL-422
l
Connect the TX- terminal on the TL8803GI to the RX- terminal on the PCL-422
l
Connect the TX+ terminal on the TL8803GI to the RX+ terminal on the PCL-422
l
2: Connect power
The maximum cable length permitted for the power connection is 100ft/30m.
Connect the GND terminal on the TL8803GI to the GND terminal on the PCL-422
l
Connect the +12V terminal on the TL8803GI to the +12V terminal on the PCL-422
l
3: Connect the PC-Link cable
Note: To ensure correct orientation, refer to items A and D in the wiring diagrams for the proper position of
the red wire on the PC-link cable.
Connect one end of the supplied PC-Link cable to the PC-Link header on the PCL-422
l
Connect the other end of the PC-Link cable to the PC-LINK_2 header on the alarm panel
l
4: Connect Ethernet (optional)
Note: Refer to item C in the wiring diagram for the correct placement of the Ethernet cable.
A Category 5 (CAT 5) Ethernet cable must be run from a source with Internet connectivity to the com-
municator module, inside the TL8803GI. The communicator end of the cable must be terminated with an RJ45
plug.
Connect one end of the Ethernet cable to the Ethernet port on the communicator
l
Connect the other end of the Ethernet cable to the Ethernet port on the router and verify that the link
l
status LED is on.
All requirements for installation of CAT5 Ethernet cable must be observed for correct operation of the
commmunicator, including but not limited to the following requirements:
Do not strip off cable sheathing more than required for proper termination.
l
Do not kink or knot the cable.
l
Do not crush the cable with cable ties.
l
Do not untwist CAT5 pairs more than 1/2 inch (1.2 centimeters).
l
Do not splice the cable.
l
Do bend the cable at right angles or make any other sharp bends.
l
Notes:
CAT5 specification requires that any cable bend must have a minimum 2 inches (5 centimeters) bend
l
radius. The maximum lenght of CAT5 cable is 328 feet (100 meters).
Before leaving the premises, the Ethernet communication lines must first be connected to an approved
l
(acceptable to local authorities) type NID. All wiring must be performed according to the local electrical
codes.
5: Connect external antenna (optional)
Upgraded antennas are available for the TL8803GI if there is inadequate cellular reception at the preferred
mounting location. Contact DSC technical support for antenna options.
The TL8803GI has two covered access ports on the top of the enclosure. Remove the plastic tab covering the
desired port and either mount the antenna on the enclosure or use the opening to pass through the antenna cable.
Note: Due to the curvature of the enclosure, the plastic port covers are NOT interchangeable. Ensure that any
unused ports are covered with their original plastic tab.
- 10 -