Tabla 29. Especificaciones de reducción de valores nominales de temperatura de funcionamiento
Reducción de valores nominales de temperatura de
funcionamiento
Hasta 35 °C (95 °F)
De 35 °C a 40 °C (de 95 °F a 104 °F)
De 40 °C a 45 °C (de 104 °F a 113 °F)
Referencias relacionadas
Temperatura de funcionamiento ampliada
Identifier
Version
Status
Particulate and gaseous contamination specifications
The following table defines the limitations that help avoid any equipment damage or failure from particulates and gaseous
contamination. If the level of particulates or gaseous pollution exceed the specified limitations and result in equipment damage
or failure, you may need to rectify the environmental conditions. Re-mediation of environmental conditions is the responsibility
of the customer.
Table 30. Particulate contamination specifications
Particulate contamination
Air filtration
Conductive dust
Corrosive dust
Table 31. Gaseous contamination specifications
Gaseous contamination
Copper coupon corrosion rate
Silver coupon corrosion rate
NOTE:
Maximum corrosive contaminant levels measured at ≤50% relative humidity.
40
Especificaciones técnicas
on page 41
GUID-CC72FD5A-E02D-4BC7-A091-30EAFCFB47B0
2
Released
Especificaciones
La temperatura máxima se reduce 1 °C cada 300 m (1 °F/547
pies) por encima de los 950 m (3117 pies).
La temperatura máxima se reduce 1 °C/175 m (1 °F/319 pies)
por encima de los 950 m (3117 pies).
La temperatura máxima se reduce 1 °C/125 m (1 °F/228 pies)
por encima de los 950 m (3117 pies).
Specifications
Data center air filtration as defined by ISO Class 8 per ISO
14644-1 with a 95% upper confidence limit.
NOTE:
This condition applies only to data center
environments. Air filtration requirements do not apply to IT
equipment designed to be used outside a data center, in
environments such as an office or factory floor.
NOTE:
Air entering the data center must have MERV11 or
MERV13 filtration.
Air must be free of conductive dust, zinc whiskers, or other
conductive particles.
NOTE:
This condition applies to data center and non-data
center environments.
● Air must be free of corrosive dust.
● Residual dust present in the air must have a deliquescent
point less than 60% relative humidity.
NOTE:
This condition applies to data center and non-data
center environments.
Specifications
<300 Å/month per Class G1 as defined by ANSI/
ISA71.04-1985.
<200 Å/month as defined by AHSRAE TC9.9.