The monobloc DUNGS Model MB-ZRDLE is made up of:
a) Minimum gas pressure switch (3) and maximum gas pressure (12)
b) Gas filter (6)
c) Pressure regulator (stabilizer) (2)
d) Safety valve (incorporate in the pressure regulator) which opens and closes rapidly (4)
e) Principle valve with two positions (lst flame and 2nd flame) which opens slowly with an adjustable initial rapid
release and rapid closing (8).
Before proceeding with regulation, read the following:
1) It is possible to reach the gas filter (6) in order to clean it, by removing one of the two side closing plates.
2) The pressure stabilizer can be regulated (see table) by manoeuvring it's regulating screw. it can be reached by
sliding the cover (2) to one side. The complete run from the minimum to the maximum position and viceversa
is about 60 turns. Do not force against the end-of-the-run position. Before starting up the burner, give the
screw at least 15 turns towards the + sign. Around the screw are arrows with symbols which indicate the sense
of rotation to increase the pressure (in a clockwise direction) and the sense of rotation to decrease pressure (in
an anti-clockwise direction). The stabilizer hermetically closes from "upstream" to "downstream" when there is
no gas flow. Different springs to obtain different pressure values from those descrive above are not foreseen.
To regulate the pressure stabilizer, connect a water manometer to the rubber tube holder installed on
the valve, to tap Pa (7), in correspondence with the stabilizer exit.
3) It is not necessary to regulate the rapid opening and closing safety valve (4).
4) Principle valve (8).
Regulating the initial rapid release effects the 1st and 2nd opening positions of the valve. Regulation of the rapid
release andof the hydraulic brake modify the 1st and 2nd positions of the valve in proportion to the output regulated.
To carry out regulation, unscrew the protection cover (11) and use the back part of it as a tool to turn the pin.
Rotation in a clockwise direction = minor rapid release
Rotation in an anti-clockwise direction = greater rapid release
REGULATING THE FIRST POSITION (1
Loosen the screw with the protruding cylindrical head (1) Give the knob (10), which regulates the output for the 2nd
flame, at least one turn in the direction of the arrow which indicates the +sign (anti-clockwise direction).
Rotate the regulating ring (9) of the 1st flame in the direction indicated by the arrow towards the + sign (anti-clockwise
direction). As an indication, this should be a little more than two turns from the end-of-the-run position. Then, when
the lst flame only is alight, rotate adequately ring (9) in order to obtain the gas delivery desired. The complete run
of the output regulator, from the - position to the + position, and viceversa, is about three and a half turns. Rotation
of the regulator in a clockwise direction, determines a reduction in delivery; rotation in an anticlockwise direction
increases delivery.
REGULATING THE SECOND POSITION (2
Loosen the screw with the protruding cylindrical head (1).
Rotate the knob (10) in the direction indicated by the arrow for the + sign (anti-
clockwise direction) as much as considered necessary in order to obtain the gas
delivery required for the 2nd flame. The complete run of the regulator from the
- position to the + position, and viceversa, is about FIVE turns. Rotate in a
clockwise direction to determine a reduction in delivery and in an anti-clockwise
direction to increase it.
After regulatiny._the gas delivery for the 1
tighten home the screw (1) to avoid the regulator moving out of the
position at which it has been set.
VALVE
INLET MAX PRESSURE
MODEL
MB ...B01 S 20
COMBINED DUNGS GAS VALVE (monobloc)
MOD. MB-ZRDLE...B01
ST
st
and 2
(PE) mbar
360
FLAME)
ND
FLAME)
nd
flame, remember to
ADJUSTTABLE OUTLET PRESSURE
FROM THE STABILIZER (PA) mbar
from 4 to 20
26
N° 0002910311
REV.:13/01/2004
DETAILS OF TERMINAL BOARD
FOR VALVE MB-ZRDLE
1st POSITION
2nd POSITION
TYPE OF GAS
Gas maturale / L.P.G.

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Btg6pBtg11p

Tabla de contenido