Use of the RS485 Bus Terminator
Fig. 1
Fig. 2
Using MICROMASTER 420/430/440 with RS485 communication requires a proper termination at both ends of the bus (between P+ and
N-), and correct pull up/ pull down resistors at at least one end of the bus (e.g. from P+ to P10, and N- to 0V).
When the MICROMASTER drive inverter is the last slave on the bus (Fig 2 on the right), and there are no other pull up/pull down
resistors on the bus, the supplied terminator must be connected shown in Fig.1.
When the MICROMASTER is the first slave on the bus (Fig. 2) the RS485 Terminator may be used to terminate the bus by using P+
and N- only, for the bus is powered by the last drive as explained.
Note: The supply for the pull up/ pull down resistors must be available whenever RS485 communication is in progress! Further
information is available in FAQ : ID 12462284 of the Siemens Drive Support in the Net:
http://support.automation.siemens.com
Der Einsatz des MICROMASTER 420/430/440 in einer RS485-Bus-Kommunikation erfordert 1. eine Stromversorgung und 2. an beiden
Bus-Enden einen Abschlusswiderstand zwischen P+ und N-).
Ist der Umrichter der letzte Slave auf dem Bus (im Bild 2), so ist dort P+ und N- des beiliegenden RS485 Terminators mit den RS485
Klemmen wie gezeigt (Bild 1) zu verbinden. P10 und 0V können zur Stromversorgung mit Klemme 1 und 2 verbunden werden.
Ist der Umrichter der erste Slave (Bild 2, links), so braucht man dort nur den Bus mit P+ N- zu terminieren. Zu beachten: Die
Stromversorgung mittels Pull-Up-/Pull-down-Widerständen muss immer zur Verfügung stehen, wenn die RS485 Kommunikation läuft!
Weitere Informationen finden Sie in der FAQ Nr. (ID) 12462284 vom Siemens Drive Support unter
20
(type 12462284 in the search box).
MICROMASTER 420/430/440, Getting Started Guide 10/14 - A5E02779537A3
http://support.automation.siemens.com