Figure 2

WIRING DIAGRAM

SUPPLY
WIRE
SUPPLY
WIRE
3.
Re-install back cover/heat sink and tighten all nine (9) mounting screws to 22 in.-
lbs. (2.5 N-m). Be sure wires are not pinched during cover installation.
Replace any damaged or missing cover screws. Use only stainless steel
#10-24 x 0.75"cover screws.
4.
To make final vertical adjustment, loosen the pivot bolts on the floodlight yoke to
position floodlight at the desired angle.
5.
Rotate the floodlight housing to the desired position.
6.
Tighten the two (2) pivot bolts to 45 ft.-lbs. (61 N-m).
7.
Turn power on.
To avoid ignition of the hazardous atmospheres or overheating of the
floodlight:
Do not position the floodlight beyond the aiming range limits.
IF 1737 • 08/17
3L WIRING, UNV1 & UNV34
BRN
L
INPUT
N
BLU
DRIVER 1
RED
+
- OUTPUT
TERMINAL
BLK
L
BRN
N
BLU
G
GRN
BLOCK
5L - 7L WIRING, UNV1 & UNV34
BRN
L
INPUT
N
BLU
DRIVER 1
BRN
RED
+
OUTPUT
TERMINAL
-
BLK
L
N
BLU
G
GRN
BLOCK
Figure 3
Figure 4
WARNING
Copyright
Input wire location
Input wire location
P2
2+
P4
SUPPLY
WIRE
PUR/BLK
1+
PUR/RED
1-
P3
2-
P1
P2
2+
P4
SUPPLY
WIRE
PUR/BLK
1+
PUR/RED
1-
P3
2-
P1
MAINTENANCE
Perform visual, electrical and mechanical inspections on a regular basis. The
environment and frequency of use should determine this. However, it is
recommended that checks be made at least once a year. We recommend an
Electrical Preventive Maintenance Program as described in the National Fire
Protection Association Bulletin NFPA 70B: Recommended Practice for Electrical
Equipment Maintenance (www.nfpa.org).
The lens should be cleaned periodically to ensure continued lighting performance.
To clean, wipe the lens with a clean, damp cloth. If this is not sufficient, use a
mild soap or a liquid cleaner such as Collinite NCF or Duco #7. Do not use an
abrasive, strong alkaline or acid cleaner. Damage may result.
Visually check for undue heating evidenced by discoloration of wires or other
components, damaged parts or leakage evidenced by water or corrosion in the
interior. Replace all worn, damaged or malfunctioning components and clean
gasket seals before putting the luminaire back into service.
Electrically check to make sure that all connections are clean and tight.
Mechanically check that all parts are properly assembled.
If the lens cover is removed from the fixture, the bezel gasket must be replaced
to maintain restricted breathing ratings.

REPLACEMENT PARTS

Crouse-Hinds Champ LED Floodlights are designed to provide years of reliable lighting
performance. However, should the need for replacement parts arise, they are available
through your authorized Crouse-Hinds distributor. Assistance may also be obtained
through your local Crouse-Hinds Sales Representative or the Crouse-Hinds Sales
Service Department, 1201 Wolf Street, Syracuse, New York 13208, Phone 866-764-
5454.
2017, Eaton's Crouse-Hinds Division
®
B
Ground lug location
Ground Lug Location
(Torque to 25 in.-lbs.)
(torque to 25 in.-lbs.)
9L - 15L WIRING, UNV1
BRN
L
INPUT
N
BLU
DRIVER 1
BRN
RED
+
- OUTPUT
TERMINAL
BLK
PUR/BLK
L
BRN
BLU
PUR/RED
N
BLU
YLW/RED
G
BLK
YLW/BLK
BLOCK
+
OUTPUT
-
RED
GRN
DRIVER 2
BLU
L
INPUT
N
BRN
9L - 15L WIRING, UNV34
BRN
L
INPUT
N
BLU
DRIVER 1
RED
+
TERMINAL
- OUTPUT
BRN
BLK
PUR/BLK
L
BLK
BLU
PUR/RED
N
WHT
YLW/RED
BRN
BLU
G
BLK
YLW/BLK
BLOCK
+
OUTPUT
GRN
-
RED
DRIVER 2
BLU
L
INPUT
N
BRN
Mounting
screw
Mounting Screw
(torque to
(Torque to 19 in.-lbs.)
19 in.-lbs.)
P2
2+
P4
1+
1-
P3
2-
P1
P2
2+
P4
1+
1-
P3
2-
P1
Page 2