Troubleshooting (Continued)
Problem
Unit will not exercise.
Excessive Vibration
Odor of fuel
Utility power returns, unit does not stop
Cause
1.
Control board not set to AUTO.
2.
Exercise timer not set or set to OFF.
3.
Unit date and time not set.
4.
Failed battery.
5.
15 Amp fuse missing or blown.
6.
Overload fuse blown.
1.
Loose mechanical fastener.
1.
Fuel leak.
1.
Blown fuses in transfer switch.
2.
5 minute minimum runtime not lapsed.
3.
Poor wire connection or defective
controllers.
Correction
1.
Press AUTO button on control board.
2.
Set exercise timer.
3.
Set unit date and time.
4.
Replace battery.
5.
Install (new) 15 Amp fuse. See System
Control Board.
6.
Check with Multimeter or contact local
service provider.
1.
Check and repair or contact local
service facility.
1.
Turn off manual shutoff fuel valve.
Contact local service facility.
1.
Install (new) fuses.
2.
Wait 5 minutes.
3.
Check, repair or contact local service
facility.
29