Burner Installation; Hydraulic Circuit - Ecoflam MAIOR P 150.1 PR Manual Del Usuario

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 23
420010244903 Maior P 150.1 PR /200.1 PR
EN
1
1
2
MAXIMUM LENGTH OF SUCTION LINES FOR TWO-PIPE SYSTEM
Two-pipe siphon feed system
Two-pipe lift system
To correct length of pipes is calculated by summing up the length of all vertical and horizontal right sections and bends. The static
suction head will be the distance between the non-return valve and the burner's pump axle. The depression must not be greater
than 0.45 bar; should it be higher, some damages could occur to the pump, with consequent increase in mechanical noises and
,eventually, a failure.

BURNER INSTALLATION

2
3
1
4 5

HYDRAULIC CIRCUIT

4
5
1 -
HOSE
3
2 -
OIL FILTER
3 -
OIL COCK
4 -
SUCTION
5 -
RETURN
H
10
6
7
1 - BURNER
2 - NUT
3 - WASHER
4 - GASKET
5 - BOLT
6 - BOILER
7 - GASKET
V2
V1
Pipe length
H (m)
AJ 6
(m)
ø 14 mm ø 16 mm
0
22
38
0,5
25
45
1
30
50
2
35
60
3
38
70
3,5
40
80
Pipe length
H (m)
AJ 6
(m)
ø 14 mm ø 16 mm
0
25
45
0,5
20
38
H
1
18
33
2
10
20
3
5
10
3,5
2
4
J 7
(m)
ø 14 mm ø 16 mm
16
29
18
33
20
37
44
25
29
52
31
55
J 7
(m)
ø 14 mm ø 16 mm
29
16
14
26
12
22
14
7
3
7
4
1