10 – Display and Configuration
1
10-5-4 Charger Setup
Use " " or " " to select "CHARGER", then press "
2
1
From the "CHARGER CURRENT" screen, use the scroll buttons
( , ) to select the desired setting and press the enter button
(
) to confirm the setting. Note: The default charger current
setting is 7A.
Each internal power module has a 5 amp charger. Charger current
3
can be set from a minimum of 2 amps total to a maximum of 5
amps per internal power module, multiplied by the number of
modules. For example, the SU60KX has three internal power
modules, so its charger current range is 2-15 amps. Set the
4
charger current value based on the size of the battery system. See
Section 10-5-3
for more information about determining the size
of the battery system.
Warning: Setting the charger current too high may damage
batteries and reduce their operational lifespan. Consult the
5
factory for guidance before changing the default setting.
Press " " or " " to change the charging current, then press
2
"
" to confirm.
6
Press "ESC" to return to the "UPS SETUP" menu.