Battery Start-Up Procedure (Single Ups) - Tripp-Lite SmartOnline SU20KX El Manual Del Propietario

Ocultar thumbs Ver también para SmartOnline SU20KX:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

9 – Start-Up, Shutdown and Bypass
1
9-3 Standard Start-Up Procedure (Single UPS)
3
Switch on the bypass input breaker switch
2
circuit breaker switch
LCD screen will show "ON AUTO BYPASS", the "BYPASS"
LED will illuminate and UPS system output will be supplied by
the bypass (reserve) power source.
3
4
Switch on the main input circuit breaker switch
4
input power source is normal, the UPS system is ready for start-up.
5
Press the ON button
5
release the button. The inverter will activate and synchronize with
6
the bypass source, then automatically switch from auto bypass
(reserve) mode to online (normal) mode. The "BYPASS" LED will
darken and the "NORMAL" LED will illuminate.
7

9-4 Battery Start-Up Procedure (Single UPS)

8
Note: The battery must be at least partially charged for this operation to succeed.
If there is an external battery cabinet connected, switch on the
1
circuit breaker
A
of the external battery cabinet. On the SU20KX
or SU40KX, turn on the battery breaker on the back of the UPS.
9
10
2
Confirm that the manual bypass circuit breaker switch
11
12
Press the ON button
3
release the button. The inverter will activate and use stored DC
battery power to supply AC power to connected equipment. The
13
"BATTERY" LED will illuminate.
14
Q2
and then output
. After a brief initialization process, the
Q4
. If the AC
Q1
A
for 3 seconds (until you hear a beep), then
A
for 3 seconds (until you hear a beep), then
(continued)
(continued)
Q4
Output
3
Output
4
5
1
is off.
Q3
Output
2
3
26
Q2
Manual
Bypass
Main
Bypass
Input
Input
Q1
Manual
Bypass
Main
Bypass
Input
Input
A
A
Q3
Manual
Bypass
Main
Bypass
Input
Input
A

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Smartonline su40kxSmartonline su60kxSmartonline su80kx

Tabla de contenido