Power Connections - BIEMMEDUE GE 125 AGRI Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 25
Warning
Make sure that the ropes and/or chains form an angle not
more than 5° with vertical to the ceiling, that the ropes do
not cross, and that a different rope is used for each hook.
The minimum distance from surrounding walls, floor and/or ceiling
must always be at least 1 metre.

4.2. POWER CONNECTIONS

Warning
The power line must be earthed and fitted with a residual
current circuit breaker.
The power cable must be connected to a panel fitted with
a cut-out.
Before switching on the heater and, therefore, before plugging it into
the electrical power supply, check that the power supply
specifications are the same as those stated on the identification
plate.
Warning
The heater is fitted with a temporary power cable, used for
the working test.
Warning
The temporary power cable must be removed and replaced
with a H07RN-F cable having a section of at least 1.5
mm
: a larger section is required if the cable is more than
2
25 metres long.
The cable must be stripped, leaving the earth lead at least
2 cm longer.
If any room thermostat or other accessories are connected to the
system (such as the timer for example) this must be done by
connecting the electrical cable to the thermostat plug (c):
• Take the plug (c) out of the power switchboard, open it and
remove the electrical jumper between terminals 2 and 3 of the
plug;
• Connect the thermostat electrical cable to terminals 2 and 3 of the
thermostat plug (c);
• Close the plug again and plug it back into the power switchboard.
Warning
Never attempt to switch the heater on or off by connecting
the room thermostat (or other control devices) to the
electrical power line.
L-L295.00-BM
NO
EN
The installation and connection of all the other accessories are
described in the specific instructions included with each accessory,
together with operating instructions.
The electrical diagram shown in this manual refers to the electrical
connection only.
4.3. CONNECTION TO FUEL SUPPLY
Warning
The heater must be installed, set up, and used in
compliance with all applicable regulations.
Connection to the diesel supply pipe can be made by connecting the
fuel tank to the burner pump:
• directly, i.e., by using the burner's diesel pump, in conformity to
the dimensions and lengths specified in the burner instruction
manual attached hereto.
• indirectly, i.e., by using an auxiliary diesel circulation pump. In this
case, contact a Customer Service Centre to ensure correct sizing
of the fuel system.
4.4 REGULATING COMBUSTION AND ANALYSING COMBUSTION
PRODUCTS
Warning
The factory setting of the burner is indicated in the
"TECHNICAL SPECIFICATIONS TABLE" and highlighted in
grey.
You may have to change the setting due to the fuel used and/or
installation conditions (high altitude, air suction pipe with or without
Snorkel) if combustion parameters are not correct.
Combustion is clean and stable when combustion values are as
follows:
Bacharach index: 0 (white)
5. OPERATING INSTRUCTIONS
5.1 START-UP
To start the space heater:
• Make sure the switch (b) is set to "0";
• Switch on power to the heater by means of the isolation switch
on the power switchboard;
• Preset the post-ventilation mode (the ventilation for cooling the
space heater when the flame is turned off) by setting
commutator (g) to position (0) for timed post-ventilation (90
sec after the flame goes out the fan stops as well) or to
position (I) for continuous post-ventilation (the fan works
continuously);
• Move the switch (b) to position (I);
• Operation will only be automatic if a thermostat or another
control device is connected to the thermostat plug (c).
• If after these operations, the generator does not work, refer to
the "FAULTS, CAUSES AND REMEDIES" section and find the
cause.
Warning
In case of safety stop, you have to push the reset button
(a) for 3 seconds to restart the heater.
Warning
NEVER do more than two restarts in a row: unburned fuel
can accumulate in the combustion chamber and suddenly
flare up at the next restart.
21 / 40