3.2.3 Drive efficiency (CDM)
The IE classification of the complete drive module (CDM) is based on the drive losses. The loss determination is
based on factory settings such as the default switching frequency. The efficiency of RSI is determined as
efficiency class IE2 according to EN 50598-2 and IEC 61800-9.
Different operating points of RSI depending on the relative torque-producing current and the relative motor
stator frequency
Pos.
A
B
Efficiencies and standby losses of RSI at different operating points
Drive efficiencies for low voltage range (3 × 208-240 V), IP66 variant
Variant,
Apparent
Nominal
power
power
current
[kW (hp)]
[kVA]
[A]
1.5 (2)
3.2
8
2.2 (3)
4.4
11
3.0 (4)
5.0
12.5
4.0 (5)
7.2
18
5.5 (7.5)
9.6
24.2
7.5 (10)
12.3
31
11 (15)
19.1
48
15 (20)
24.7
62
B [ % ]
10
10
10
Standby
losses
25
50
100
[W]
1
2
3
14
1.89 2.10 2.61 1.94 2.23 2.93 2.00 2.43 3.46 2.01 2.46 3.58
14
1.62 1.86 2.42 1.69 2.01 2.81 1.74 2.24 3.49 1.76 2.29 3.66
14
1.55 1.79 2.39 1.61 1.95 2.81 1.65 2.21 3.56 1.67 2.27 3.74
14
1.36 1.57 2.06 1.42 1.69 2.34 1.47 1.85 2.76 1.48 1.90 2.87
14
1.04 1.29 2.00 1.10 1.42 2.35 1.14 1.61 2.93 1.15 1.65 3.07
14
0.97 1.23 1.99 1.03 1.37 2.40 1.07 1.59 3.10 1.09 1.64 3.27
18
1.07 1.32 2.04 1.13 1.46 2.42 1.18 1.65 3.04 1.19 1.70 3.19
18
0.99 1.26 2.03 1.06 1.41 2.47 1.11 1.64 3.23 1.12 1.69 3.42
Description
Relative torque-producing current
Relative motor stator frequency
Frequency[%]
50
50
50
90
Current [%]
25
50
100
25
Operating point
4
5
6
7
Relative losses [%]
90
90
100 100 100
50
100
25
50
100
8
9
10
11
12
15