Output Parameters - gefran 40T 48 Manual De Instrucciones

Ocultar thumbs Ver también para 40T 48:
Tabla de contenido

Publicidad

• TC / LIN input parameters
(. I .
Select sampling
time (resolution).
For linear input only.
F. t
Digital filter
on main input
Digital filter on
f. d
process variable
display
d. P .
Decimal point
position for main
input scale
+4 to display Lo below value LS-(HS-LS)/256 (non-
custom linear inputs only)
(*) not available for scales TC, RTD, PTC, NTC
Minimum limit of
l. s
main input scale
and analogue output
Maximum limit of
x. S
main input scale
and analogue output
Offset correction
oF.
of main input
0
d. 1 .
Select
1
function of
2
digital input
3
4
5
t. U .
Raise key
6
function active
7
only in
8
P.V.selection
9
10
11
t. d .
Lower key
12
function active
13
only in
14
P.V.selection
15
16
17
18
19
L. L
Low limit for the
alarms set point
x. L
High limit for
the alarms set point
0
120ms
> 14bits 16000 points
1
60ms
> 14bits 16000 points
2
30ms
> 13bits 8000 points
3
15ms
> 12bits 4000 points
+4 to disable digital filter F.t (average
of the last eight values sampled)
0.0...20.0 sec
0.0...9.9
scale points
dP
Format
0
XXXX
1
XXX.X
2 *
XX.XX
3 *
X.XXX
min...max scale
of input selected
in t.P
min...max scale
of input selected
in t.P
-999...999
scale points
d. I . - t. u. - t. d.
None
Zero
Hold
Flash
Max. peak display
Min. peak display
Delta peak display
Peak memory reset
Zero + peak memory reset
Alarms reset
Peak + alarms reset
Zero + alarms reset
Peak + zero + alarms reset
Output status OUT1
Output status OUT2
Output status OUT3
Output status OUT4
Blocked keyboard (only d. 1 . )
Potentiometer Calibration
(only t. U . and t. d . )
OFFSET (only t. U . and t. d . )
L.S ... H.S
L.S ... H.S

• Output parameters

0v
Output settings
0. n
Number of outputs
1. t
Alarm type 1
(absolute only)
2. t
Alarm type 2
3. t
Alarm type 3
4. t
Alarm type 4
f. 0
Output filter mode
r. a
Delay for F.O.
t. M 1
Minimum
output pulse
re
Fault action
(in case of
damaged
sensor)
Er, br.
14
0 ... 4
1. t - 2. t - 3. t - 4.t
Valore
Direct
Absolute or Normal or
(high limit)
Relative
Symmetric
Inverse
to previous (window)
(low limit)
absolute
0
Direct
Absolute
1
Inverse
Absolute
2
Direct
Relative
3
Inverse
Relative
4
Direct
Absolute Symmetric
5
Inverse
Absolute Symmetric
6
Direct
Relative
Symmetric
7
Inverse
Relative
Symmetric
+8 to disable on power-up until first
alarm
+16 to memorize
+32 to filter with F.O. mode (output filter
mode)
0 not active: calculated status
is sent directly to relay
1 On delay (DON)
2 On delay after it has
been turned off (DBI)
3 Off delay (DOF)
4 Delay for activation only
at power-up (DPO)
+ 8 time base max. 99 min
(default = 99 sec)
0 ... 99 min
or sec
0 ... 99 sec
Disabled by setting value 0
Displayed if associated with at least
one output
Value OUT 1 OUT 2 OUT 3 OUT 4
0
OFF
OFF
OFF
1
ON
OFF
OFF
2
OFF
ON
OFF
3
ON
ON
OFF
4
OFF
OFF
ON
5
ON
OFF
ON
6
OFF
ON
ON
7
ON
ON
ON
8
OFF
OFF
OFF
9
ON
OFF
OFF
10
OFF
ON
OFF
11
ON
ON
OFF
12
OFF
OFF
ON
13
ON
OFF
ON
14
OFF
ON
ON
15
ON
ON
ON
Normal
Normal
Normal
Normal
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON

Publicidad

Tabla de contenido
loading

Tabla de contenido