6. commissioning

6.1 Initialisation phase

6.2 Indication of the selected relay

6.3 Error message

The "S-Bus interface adapter" is equipped with a 7-seg-
ment LED display that can indicate the selected relay or the
current operational status.
When the interface adapter is connected to a controller
for the first time, a short initialisation phase will be run.
During this phase, the LED display flashes first the error
code f, then the error code u until the controller connect-
ed has been recognised. After a short time, the address of
the selected relay will be indicated.
If the error codes do not disappear or if an a is indicated
instead of the relay address, see chapter 6.3 for error code
descriptions and troubleshooting measures.
The relay addressed via the DIP switches is displayed by the
7-segment-LED at the front of the adapter.
As the LED can only indicate one figure, the decimal digit is
replaced with a dot when indicating relays 10 - 16:
1 = Relay 1
Regtronic RM
2 = Relay 2
3 = Relay 3
Regtronic RX
4 = Relay 4
5 = Relay 5
6 = Relay 6
7 = Relay 7
8 = Relay 8
If an error occurs, the display flashes an error code:
a = The output addressing is faulty. The relay addressed
does not exist.
Î Address a valid relay.
f = The S-Bus connection is faulty.
Î Check the S-Bus cable.
u = The controller connected is not recognised by the de-
vice.
Î Wait for about one minute. If the error code does not
disappear, contact the manufacturer.
9 = Relay 9
0. = Relay 10
1. = Relay 11
2. = Relay 12
3. = Relay 13
4. = Relay 14
5. = Relay 15
6. = Relay 16