2) Inspection of the direction of travel and power regulation
Note: invert V and W if the motor faces left (as seen from inside the device).
N.B.: in this case you need to press and hold the PROG button to operate. Operation is step by step so each press of the button stops-closes-stops-opens, etc.
The LEDs confirm whether configuration is correct, as described below.
a) Turn OFF DIP switches 1-2-3-4-5-6-7 and 8.
b) Turn ON DIP switch 1 (the DL1 LED will flash quickly)
c) Set the "TORQUE" trimmer at minimum
d) Press the PROG button (the green LED marked DL7 switches on and the gate opens)
e) Gradually increase the "TORQUE" only if necessary (WARNING: excessive torque could be dangerous
for users)
g) After opening, the end travel is pressed by the cams and the motor stops.
h) Release the PROG button (The LED marked DL7 switches off).
i) Press and hold the PROG button again (the red LED marked DL6 switches on and the gates starts to
close).
j) The end travel stops the motor when the gate is fully closed.
k) Release the PROG button (DL6 switches off).
l) Turn OFF DIP switch 1 and move to step 3.
WARNING: Make sure the electric end travels act BEFORE the gate reaches the mechanical pads of the end travel. This ensures safe operation.
3) Programming the work and pause time before automatic closure.
IMPORTANT: Bridge the COM-PHOT and COM-EDGE if the safety devices are not installed. The LEDs marked DL3 and DL4 must be switched on.
An LED that does not switch on means there is a faulty safety device or that there is no connection. The gate will be locked in place.
a) Turn ON DIP switch 2 (the LED marked DL1 will flash slowly)
b) Briefly press the PROG button (the gate opens until it meets the electrical end travel for opening). Wait for two seconds, and then press the PROG button again to set
the operating time for the gate. Once the gate has fully opened, the board counts down the time before automatic closure can begin.
NB. Automatic closure needs to be taught in even if this function is not enabled (DIP 3 switched off).
c) Wait for the required amount of time before pressing the PROG button to register the waiting time. Close the gate.
d) The gate is closed. DL1 has stopped flashing. The times are registered. Switch OFF DIP switch 2.
4) Programming the remote control
1) Turn ON DIP switch 1 and then turn ON DIP switch 2 => the LED marked DL1 will flash for 10 seconds.
2) Press the remote control button (normally channel A) within the 10 seconds. LED 2 (green) will flash to confirm the remote control is properly recorded.
3) The code programming time is automatically reset for recording the next remote control.
4) To end programming, wait for 10 seconds or briefly press the PROG button => the LED marked DL1 will stop flashing.
5) Turn OFF DIP switch 1 and turn OFF DIP switch 2.
5) Personalizing configuration
The micro-switches allow you to change the configuration
Microswitches ON
DIP3
Automatic closing activated
DIP4
Photocells active only in closing
DIP5
Outside flashing light
DIP6
Step-by-step command
DIP7
Safety strip monitoring TEST enabled
DIP8
available
IMPORTANT: The system must comply with all the standards and Directives currently in force.
Microswitches OFF
Automatic closing not activated
Photocells active all the time
Inside courtesy light
The command has no effect in opening
Safety strip monitoring TEST disabled
available
ON
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8