Grundfos UPE 2000 Serie Manual Del Usuario página 13

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 102
6.7.2 Bus module
The bus module enables serial communication with
the pump via an RS-485 input. The communication is
carried out according to the Grundfos bus protocol,
GENIbus, and enables connection to the Grundfos
Pump Management System 2000, a building man-
agement system or another type of external control
system.
Via the bus signal, it is possible to remote-set pump
operating parameters, such as desired head, tem-
perature influence, operating mode, etc. At the same
time, the pump can provide status information about
important parameters, such as actual head, actual
flow, power input, fault indications, etc.
For further details, consult the operating instructions
for the Grundfos Pump Management System 2000 or
contact Grundfos.
Note: When a bus module is fitted to the pump, the
number of settings available on the pump control
panel and via the R100 will be reduced.
The pump head and control mode can only be set via
the bus signal. The pump control panel or the R100
can only set the pump to max. curve and to stop.
However, an R100 is required if a number is to be al-
located to the pump. See also section 7.8 Priority of
settings.
In addition to the RS-485 input, the bus module has
three inputs for external signals for the forced-control
functions:
• Start/stop of pump.
• Max. curve duty.
• Min. curve duty (night-time duty).
If the pump has been forced-controlled to for in-
stance max. curve duty, the light fields on the pump
will indicate "max. curve", see section 7.3.1 Setting
to max. curve duty.
Note:
• If no external on/off switch is connected, the con-
nection across terminals 7 and 8 should be main-
tained.
• All cables used must be heat-resistant up to at
least +85°C.
• All cables used must be installed in accordance
with EN 60 204-1.
• Wires connected to
- inputs 7 to 10 and
- supply terminals
must be separated from each other and
from the supply by reinforced insulation.
• All leads connected to a terminal block
must be tied up at the terminals.
Wiring diagrams of bus module:
Fig. 17
UPE 25-40, 25-40 A, 25-60, 25-60 A, 32-40 and
32-60 with MB 40/60
BUS
4
5
6
A Y
B
7
8
9
10
Stop
Min.
Fig. 18
UPE 25-80, 32-80, 40-80 and 50-80 with MB 80
BUS
4
5
6
A Y
B
Start/stop
Start/stop
Min. kurve
Min. curve
(Natsænkning)
(night-time duty)
Maks. kurve
Max. curve
7
8
9
10
Stop
Min.
Start/stop
Start/stop
Min. curve
Min. kurve
(Natsænkning)
(night-time duty)
Maks. kurve
Max. curve
Max.
Maks.
Max.
Maks.
13

Publicidad

Tabla de contenido
loading

Tabla de contenido