Nozzle Location - Siemens SITRANS LR200 Guia De Inicio Rapido

Ocultar thumbs Ver también para SITRANS LR200:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 115
• The end of the shield section should protrude a
minimum of 10 mm (0.4") to avoid false echoes being
reflected from the nozzle.
Location on a manhole cover
• A manhole cover is typically a covered nozzle with a
diameter 610 mm (24") or greater.
• For optimum signal conditions, locate the antenna
off-center, typically 100 mm (4") from the side.

Nozzle location

WARNING: For vessels with conical or parabolic tops, avoid mounting the
instrument at the centre. (The concavity of the top can focus echoes into the centre,
giving false readings.)
Note: Under certain circumstances, it may be acceptable to mount the device at the centre of
a flat-topped tank. Please discuss this with your local Siemens representative.
Coni
Conical
Environment
• Provide an environment suitable to the housing rating and materials of construction.
• Provide a sunshield if the device will be mounted in direct sunlight.
Access for programming
• Provide easy access for viewing the display and programming via the hand programmer.
Page EN-6
SITRANS LR200 (HART) – QUICK START MANUAL
Fl
at
Flat
Parabolic
shield
preferred
undesirable
(continued on next page)
10 mm
(0.4")
100 mm (4")
A5E31993614

Publicidad

Tabla de contenido
loading

Tabla de contenido