Operating Instructions
Safety Switch SGP-TW... (Twin)
Function test
WARNING
Fatal injury due to faults during the function test.
Before carrying out the function test, make sure
f
that there are no persons in the danger zone.
Observe the valid accident prevention regula-
f
tions.
Check the device for correct function after installa-
tion and after every fault.
Proceed as follows:
Mechanical function test
The actuator must slide easily into the actuating
head. Close the guard several times to check the
function. The function of any manual releases (except
for the auxiliary release) must also be tested.
Electrical function test
1. Switch on operating voltage.
2. Close all guards.
The machine must not start automatically.
¨
3. Start the machine function.
4. Open the guard.
The machine must switch off and it must not be
¨
possible to start it as long as the guard is open.
Repeat steps 2 - 4 for each guard.
Inspection and service
WARNING
Danger of severe injuries due to the loss of the
safety function.
If damage or wear is found, the complete switch
f
and actuator assembly must be replaced. Re-
placement of individual parts or assemblies is
not permitted.
Check the device for proper function at regular
f
intervals and after every fault. For informa-
tion about possible time intervals, refer to
EN ISO 14119:2013, section 8.2.
Inspection of the following is necessary to ensure
trouble-free long-term operation:
correct switching function
f
secure mounting of all components
f
damage, heavy contamination, dirt and wear
f
Hinged actuator S-OU-SN
20
35,50
Fig. 3: Minimum door radii
sealing of cable entry
f
loose cable connections or plug connectors.
f
Info: The year of manufacture can be seen in the
bottom, right corner of the type label.
Exclusion of liability and warranty
In case of failure to comply with the conditions for
correct use stated above, or if the safety regula-
tions are not followed, or if any servicing is not
performed as required, liability will be excluded and
the warranty void.
Notes about
The following information applies to devices
with cable entry:
For use and application as per the requirements
of
a copper wire for the temperature range
60/75 °C must be used.
EU declaration of conformity
The declaration of conformity is part of the oper-
ating instructions, and it is included as a separate
sheet with the device.
The original EC declaration of conformity can also
be found at: www.euchner.com
Service
If servicing is required, please contact:
EUCHNER GmbH + Co. KG
Kohlhammerstraße 16
70771 Leinfelden-Echterdingen
Service telephone:
+49 711 7597-500
E-mail:
support@euchner.de
Internet:
www.euchner.com
Hinged actuator S-OU-LN
Hinged actuator S-LR-SN
for insertion funnel
20
35,50

Technical data

Parameter
Housing material
Degree of protection
Mechanical life
Ambient temperature
Degree of contamination
(external, acc. to EN 60947-1)
Installation orientation
Approach speed, max.
Extraction force
Retention force
Actuating force, max.
Actuation frequency
Switching principle
Contact material
Connection
Conductor cross-section
(flexible/rigid)
Operating voltage for optional
LED indicator
(only SGP-TW...538H)
Conditional short-circuit
current
Switching voltage, min.,
at 10 mA
Switching current, min., at
24 V
Short circuit protection
(control circuit fuse) acc. to
IEC 60269-1
Convent. thermal current I
Utilization category acc. to EN 60947-5-1
AC-15
DC-13
Rated insulation voltage
Rated impulse withstand
voltage
Reliability values acc. to EN ISO 13849-1
B
10D
at DC-13 100 mA/24 V
Hinged actuator S-LR-LN
for insertion funnel
5
Value
Reinforced thermoplastic
IP67
1 x 10
operating cycles
6
-20 ... +80 °C
3 (industrial)
Any
20 m/min
25 N
10 N
25 N
6,700/h
Slow-action switching contact
Silver alloy, gold flashed
Cable entry M20 x 1.5
0.34 ... 1.5 mm²
L060 12 - 60 V
L110 110 V
L220 230 V
100 A
12 V
1 mA
4 A gG
4 A
th
4 A 230 V
4 A 24 V
U
= 250 V
i
U
= 2.5 kV
imp
2 x 10
6
Door radius,
Actuator
min. [mm]
Actuator S-G...
300
Actuator S-W...
300
Hinged actuator S-OU...
200
Hinged actuator S-LR...
200