Step 2:

Hang indoor unit

1. Use the included paper template to cut a rectangular hole in the ceiling, leaving at least 1m (39")
on all sides. The cut hole size should be 4cm(1.6") larger than the boby size.
Be sure to mark the areas where ceiling hook holes will be drilled.
(A)
Refrigerant piping side Drain hose side
780mm / 30" (Suspension bolt)
840mm / 33"(Body)
880mm / 34.7"(Ceiling opening)
950mm / 37.4"(Panel)
18-48K Super-Slim models ceiling hole size
Drain hose side
Refrigerant piping side
545mm / 21.5" (Suspension bolt)
570mm / 22.4"(Body)
600mm / 23.6"(Ceiling opening)
647mm / 25.5"(Panel)
Compact models ceiling hole size
Refrigerant piping side
840mm / 33" (Suspension bolt)
900mm / 35.4" (Body)
940mm / 37.0" (Ceiling opening)
1020mm / 40.2" (Panel)
60K Super-Slim models ceiling hole size
>100cm / 39"
>100cm / 39"
Drain hose side
>100cm / 39"
>100cm / 39"
Page 23