2
Product information
2.6
Technical Data
Tank capacity
Tank capacity (total)
Maximum flow rate
Maximum DHW temperature
Maximum operating pressure DHW
Tank performance at:
Domestic cold water inlet temperature
Domestic hot water outlet temperature
DHW temperature rise
Coil supply water temperature (boiler water)
Coil flow rate (boiler water)
Coil pressure drop (boiler water)
Continuous rating
First hour rating
Maximum heat input to tank
Heat exchanger
Content
Surface area
Standby heat loss (at 149 °F (65 °C) DHW temperature, 68 °F (20 °C) room
temperature)
Maximum coil supply water temperature
Maximum coil operating pressure
Table 5 Technical Data
6
Unit
SU54/5
gal
52.8
(l)
(200)
gpm
5.3
(l/min)
(20)
°F
203
( °C)
(95)
psi
145
(bar)
(10)
°F
50
( °C)
(10)
°F
140
( °C)
(60)
°F
90
( °C)
(50)
°F
176
( °C)
(80)
gpm
11.45
(l/h)
(2600)
foh
2.68
(mbar)
(80)
gph
114
(l/h)
(430)
gpm
1.9
(l/min)
(7)
gph
151
(l/h)
(570)
btu/hr
85304
(kW)
(25)
gal
1.59
(l)
(6)
2
ft
9.69
2
(m
)
(0.9)
°F/h
0.55
(K/h)
(0.31)
°F
230
( °C)
(110)
psi
232
(bar)
(16)
SU54/5, SU80/5, SU100/5 – 6 720 808 532 (2013/08)
SU80/5
SU100/5
79.3
103
(300)
(390)
7.9
10.3
(30)
(39)
203
203
(95)
(95)
145
145
(10)
(10)
50
50
(10)
(10)
140
140
(60)
(60)
90
90
(50)
(50)
176
176
(80)
(80)
11.45
15.41
(2600)
(3500)
3.35
6.93
(100)
(207)
134
209
(507)
(791)
2.2
3.5
(8)
(13)
190
281
(717)
(1064)
100658
156959
(29.5)
(64)
2.32
3.2
(8.8)
(12.1)
13.99
19.38
(1.3)
(1.8)
0.41
0.34
(0.23)
(0.19)
230
230
(110)
(110)
232
232
(16)
(16)