Dazzle guard
This product is equipped with an integrated dazzle guard. If blinded by extraneous
light, this puts the sensor into a brightness-related evaluation mode for 60 s.
(➔ "13� Troubleshooting")
Presence detection switch-off logic
The load connected is switched OFF once the selected light level is exceeded.
Reach setting (Fig� 6�1)
Infinitely adjustable
– Control dial set to maximum = max. reach (approx. Ø 8 m)
– Control dial set to minimum = min. reach (approx. Ø 1 m)
Reach diagram (Fig� 6�2)
Time setting (Fig� 6�1)
The time you want the connected lamp to stay ON for is infinitely adjustable from
approx. 5 sec to a maximum of 15 min. Any movement detected before this time
elapses will restart the timer.
Pulse function
The pulse function activates the output for 2 s (e.g. for staircase lighting time switch-
es). The sensor will then be in a dead time for 8 seconds.
Note: is the pulse function is selected via the controller, time cannot be set by remote
control.
Manual override function (Fig� 4�1)
If a mains switch is installed in the mains supply lead, the following functions are
available in addition to simply switching ON and OFF:
Important: The switch should be actuated in rapid succession (in the 0.5 - 1 s range).
Sensor mode
1) Switch light ON (when light is OFF): switch ON and OFF once.
Sensor stays ON for the period selected.
2) Switch light OFF (when light is ON): switch ON and OFF once.
Sensor goes out or switches to sensor mode.
Manual override
1) Activate manual override:
Switch ON and OFF twice. The sensor is set to stay ON for 4 hours (red LED lights
up behind the lens). Then it returns automatically to sensor mode (red LED off).
2) Deactivate manual override:
Switch ON and OFF once. Sensor goes out or switches to sensor mode.