Waeco AirCon Service Center ASC5100G Instrucciones De Uso página 95

Estacion de mantenimiento de aire acondicionado
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

ASC5100G
✓ The device evacuates the service hoses.
8. Unscrew the service couplings from the service hoses (7) and (8).
9. Press ENTER to confirm.
✓ The device equalizes with the ambient pressure.
10. Screw the service couplings hand-tight onto the service hoses (7)
and (8), taking care not to mix up the red and blue markings on the
couplings and hoses.
11. Use the keypad (2) to enter the current local atmospheric pressure
and press ENTER to confirm.
I
NOTE
You can look up the current atmospheric pressure for your region on the
Internet, for example at http://www.meteo24.de/wetter/ under "air pres-
sure".
12. When calibration has been completed, press ENTER to exit the
menu.
13. Press STOP twice to access the standby menu.
14. To evacuate the service hoses, perform a short vacuum phase (see
chapter "Free selection" on page 87).
EN
All manuals and user guides at all-guides.com
HP/LP connectors
removed ?
Service tasks
95

Publicidad

Tabla de contenido
loading

Tabla de contenido