Filling Up The Internal Refrigerant Container - Waeco AirCon Service Center ASC5100G Instrucciones De Uso

Estacion de mantenimiento de aire acondicionado
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

ASC5100G
7.8

Filling up the internal refrigerant container

When the AirConServiceCenter is started for the first time, the internal
refrigerant vessel must be filled from an external refrigerant vessel with at
least 2000 g of refrigerant.
The unit displays error message 12.
Press STOP to confirm.
I
NOTE
Note the instructions on the refrigerant vessels.
Vessels for the R-1234yf refrigerant have a left-hand thread.
The current supply quantities are displayed in the standby menu.
There are three different types of refrigerant vessel available:
 Refrigerant vessels without rising pipe:
These refrigerant vessels have one connection.
When filling the AirConServiceCenter, the connection must be on the
bottom (turn the vessel upside down).
 Refrigerant vessels with rising pipe:
These refrigerant vessels have one connection.
When filling the AirConServiceCenter, the connection must be at the
top (place the vessel).
 Refrigerant vessels with rising pipe:
These refrigerant vessels have two connections. To top up the
AirConServiceCenter, use the connection marked with L (= liquid).
When filling the AirConServiceCenter, the connection must be at the
top (place the vessel).
1. In the basic menu, use the cursor keys  or  to select "Other
selections":
2. Press ENTER to confirm.
3. Use the cursor keys  or  to select "Int. vessel filling":
4. Press ENTER to confirm.
EN
All manuals and user guides at all-guides.com
Short selection
Free selection
Other selections
ENTER-OK
Int. vessel filling
Hybrid Service
A/C system test
ENTER-OK STOP-EXIT
Initial start-up
73

Publicidad

Tabla de contenido
loading

Tabla de contenido